Some of you have completed our Online Continuing Education Courses which include video instruction and know this is a very fast way to obtain your CEU credits from the comfort of the chair you're sitting in. For the rest of you we are sending a weekly series of newsletters featuring an instructional page complete with videos.

To view the videos you will need to download the free Real Player Download Real Player plugin for your browser - if you don't already have it. After installing Real Player, you can view the videos by clicking on one of these icons:

  • Click on this icon Hi Res - Cable/DSL if you have a cable or DSL connection.
  • Click on this iconLow Res - Modem if you have a Dial-up connection.

Below is the full course page which includes these videos:


2002 Changes to the NEC®
Article 680 Low Res - Modem Hi Res - Cable/DSL        Page 7 of 10
Swimming Pools, Fountains, and Similar Installations

680.22 Area Lighting, Receptacles, and Equipment

This subsection was revised to read:

(A) Receptacles.
(5) GFCI Protection.
All 125V receptacles located within 20 ft. of the inside walls of a pool or fountain must be protected by a ground-fault circuit interrupter. Receptacles supplying pool pump motors rated 15 or 20A, single-phase, 120V through 240V must be provided with GFCI protection. Figure 680-5

Intent: The revised text is intended to clarify that GFCI protection is required for all 15 or 20A, 120V through 240V,240V circuits that supply single-phase receptacles for pool pump motors.


Figure 680-5
Click on Image to Enlarge

Copyright © 2004 Mike Holt Enterprises,Inc.