Print This Newsletter
Code Basics: Article 725
By Mike Holt for EC&M Magazine
Looking at some highlights of
Article 725 will help you better understand specialized low-power
circuit requirements.
Article 725 contains the
requirements for remote-control, signaling and power-limited
circuits that are not integral to a device or appliance. It
includes circuits for burglar alarms, access control, sound,
nurse call, intercoms, some computer networks, some lighting
dimmer controls, and some low-voltage industrial controls.
As with all other Articles in
Chapters 5 through 8, the wiring methods required by Chapters 1
through 4 apply. But, Article 725 specifies conditions where
these methods are not required. In fact, the purpose of Article
725 is to allow for the fact that these circuits are
characterized by usage and power limitations that differentiate
them from electric light and power circuits. Article 725
provides alternative requirements for minimum wire sizes,
adjustment factors, overcurrent protection, insulation
requirements, wiring methods, and materials.
Class X Circuit Requirements
Circuits covered by Article 725
will fall into one of three classes, as summarized by Figure 725-6
un725-06 725-02 06 def sum.cdr:
Note: Graphics are not included in
this newsletter.
- Class 1. That portion of the
wiring system between the load side of the circuit
overcurrent device and the connected equipment. The Code
sections specific to Class 1 are 725.21 through 725.29.
- Class 2. That portion of the
wiring system between the load side of a Class 2 power
source and the connected equipment. Class 2 circuits
consider safety from a fire initiation standpoint and
provide protection from electric shock by limiting the
current [Chapter 9 Table 11(A)]. The Code sections
specific to Class 2 are 725.41 through 725.71.
- Class 3. That portion of the
wiring system between the load side of a Class 3 power
source and the connected equipment. Class 3 circuits
consider safety from a fire initiation standpoint.
Because these circuits permit dangerous voltages-up to
100V for an inherently limited power source [Chapter 9
Table 11(A)]-the Code contains additional requirements to
safeguard against electric shock. The Code sections
specific to Class 3 are the same as those for Class 2.
Some mechanical details
[725.5] Locate cables so they dont
prevent access to equipment. Route them so they dont
prevent ceiling panels to be moved (see Figure 725-15 un725-15
725-05.cdr).
[725.6] The neat and
workmanlike manner rule applies here, as in other places.
Support cables to prevent damage from normal operation. Use
hangers and other devices designed to eliminate or minimize
damage to the cable. If you install cables in or near framing
members, protect them against penetration by screws or nails. To
do this, provide a 1.25 in. separation from the face of the
framing member or use a suitable metal plate in accordance with
300.4(D). See Figure 725-17 un725-17 725-06 02 300-04D.cdr.
[725.8] Where damage to remote-control
circuits of safety control equipment would introduce a hazard [725.8(A)],
provide a suitable means of protection, such as rigid metal
conduit.
Class 1 Highlights
Of the three classes, this one has
the tightest limitations on power levels. If you exceed those
power levels, you are no longer at Class 1 and must then adhere
to stricter standards of materials and installation. Here are
some key points to remember:
- [725.21] Class 1 power-limited
circuits can be AC or DC, but must be supplied from a
power source that limits the output to 30V with no more
than 1000 VA (see Figure 725-20 un725-20 725-21A.cdr).
- Class 1 remote-control and
signaling circuits shall not operate at more than 600V.
But, there is no requirement to limit the VA output of
the power supply. One of the most common applications of
a Class 1 control circuit is the operating coil for a
magnetic motor starter or lighting contactor. This would
include coils at 120V, 220V and 460V (see Figure
725-21 un725-21 725-21B.cdr).
- A magnetic motor starter
having the coil wired to a motor control circuit (tapped
from the motor branch circuit) is not a Class 1 circuit.
See 725.3(F) and 430.41.
- [725.26] Two or more Class 1
circuits can be in the same cable, enclosure or raceway.
- Class 1 circuits can be in
the same cable, enclosure or raceway with power supply
circuits, only where the equipment powered is
functionally associated with the Class 1 circuit (see Figure
752-23 un725-23 725-26B1.cdr).
- [725.27] Flexible cords
installed in accordance with Article 400 are permitted.
- Class 1 circuit conductors
must have a 600V insulation rating and comply with Table
310.13 or Table 402.3.
Class 2 and Class 3
The NEC does not require you to
install Class 2 and 3 in a raceway. But, if you do install them
in a raceway, you should do so per the BICSI Cabling Installation
Manual. This installation guideline recommends that raceway runs:
- Be limited to 100 ft
- Have no more than two 90-degree
bends
- Have a maximum pull force of
25 pounds for Category 5 cable
- Have a maximum pull force of
100 pounds for optical fiber cable.
Because most installers have no
idea how to limit the pulling tension on signal or communication
cables, the generally accepted practice is to size the raceway so
the cables do not exceed the percentage fill listed in Chapter 9,
Table 1 of the NEC.
Power sources
[725.41] The power source for a
Class 2 or a Class 3 circuit must be one of the following:
- A listed Class 2 or Class 3
transformer.
- A listed Class 2 or Class 3
power supply.
- Equipment listed as a Class 2
or Class 3 power source (amplifier for audio program
signals).
- Listed information technology
equipment.
- A dry cell battery, provided
the voltage is 30V or less for a Class 2 circuit.
Wiring
- [725.42] Equipment must be
marked to indicate each circuit that is Class 2 or Class
3.
- [725.51] Conductors and
equipment on the supply side of the Class 2 or Class 3
power source must comply with the requirements in
Chapters 1 through 4.
- [725.52] and [725.25]
Conductors and equipment on the load side of the Class 2
or Class 3 power source can use a Chapter 3 wiring method.
There are exceptions to this.
- Where it is necessary to
install Class 2 or Class 3 circuits inside the same
raceway or cable with power or Class 1 circuits, you can
reclassify Class 2 or Class 3 circuits. To do so, the
conductors must have 600V insulation. Further, you must
remove the Class 2 or Class 3 marking on the equipment,
and provide overcurrent protection in accordance with 725.23.
If you reclassify Class 2 or Class 3 circuits as Class 1
circuits, you cant install them with other Class 2
or Class 3 circuits that have not been reclassified as
Class 1.
Separation from Other Systems
- [725.55] As indicated
earlier, you cant Class 2 or Class 3 circuit
conductors in any enclosure, raceway or cable with
conductors of power or Class 1 conductors.
- You can install Class 2 and
Class 3 circuits with Class 1, non-power-limited fire
alarm and medium power network-powered broadband
communications circuits, if you separate them with a
barrier (see Figure 725-30 un725-30 725-55B.cdr).
- Inside an enclosure, you can
run Class 2 and Class 3 circuits in a raceway to separate
them from Class 1, non-power-limited fire alarm and
medium power network-powered broadband communications
circuits.
- You can mix Class 2 and Class
3 conductors with power conductors in boxes or
enclosures, if the power circuit conductors are
introduced solely to connect to the equipment connected
to Class 2 and 3 circuits and you meet certain spacing
and voltage requirements.
- You can put mix Class 2
conductors with other Class 2 conductors and Class 3
conductors with other Class 3 conductors. But, if you mix
Class 2 conductors with Class 3 conductors, you must use
Class 3 wiring methods for the Class 2 conductors.
Lightning
[725.57] Underground installations
are not considered exposed to lighting. To reduce electromagnetic
interference and to reduce damage from voltage surges, the
practice is to ground one end of underground cables (Figure
725-33 un725-33 725-57.cdr). Where Class 2 or Class 3
circuits run overhead between buildings, they are susceptible to
lightning. The conductors must maintain at least 6 ft separation
from lightning conductors. You must also ground (or interrupt)
the metallic sheath as close as practicable to the point of
entrance. Where grounded, follow 800.40 or 820.40 as applicable.
Article 725 consists of three
parts. Part I provides general information, Part II pertains to
Class 1 cabling, and Part II pertains to Class 2 and 3 cabling.
The key to understanding and applying each of the three parts is
knowing the voltage levels of the cabling involved and the
purposes of that cabling. Article 725 allows you to save time and
money when working with particular types of circuits. Thus, its
a good investment for people who work with low-power circuits to
become familiar with Article 725.
Click here to view the survey results from this newsletter.
Copyright © 2002 Mike Holt Enterprises,Inc.
1-888-NEC-CODE (1-888-632-2633)