Print This Newsletter

Code Basics: Article 725
By Mike Holt for EC&M Magazine

Looking at some highlights of Article 725 will help you better understand specialized low-power circuit requirements.

Article 725 contains the requirements for remote-control, signaling and power-limited circuits that are not integral to a device or appliance. It includes circuits for burglar alarms, access control, sound, nurse call, intercoms, some computer networks, some lighting dimmer controls, and some low-voltage industrial controls.

As with all other Articles in Chapters 5 through 8, the wiring methods required by Chapters 1 through 4 apply. But, Article 725 specifies conditions where these methods are not required. In fact, the purpose of Article 725 is to allow for the fact that these circuits “are characterized by usage and power limitations that differentiate them from electric light and power circuits.” Article 725 provides alternative requirements for minimum wire sizes, adjustment factors, overcurrent protection, insulation requirements, wiring methods, and materials.

Class X Circuit Requirements

Circuits covered by Article 725 will fall into one of three classes, as summarized by Figure 725-6 un725-06 725-02 06 def sum.cdr:

Note: Graphics are not included in this newsletter.

Some mechanical details

[725.5] Locate cables so they don’t prevent access to equipment. Route them so they don’t prevent ceiling panels to be moved (see Figure 725-15 un725-15 725-05.cdr).

[725.6] The “neat and workmanlike manner” rule applies here, as in other places. Support cables to prevent damage from normal operation. Use hangers and other devices designed to eliminate or minimize damage to the cable. If you install cables in or near framing members, protect them against penetration by screws or nails. To do this, provide a 1.25 in. separation from the face of the framing member or use a suitable metal plate in accordance with 300.4(D). See Figure 725-17 un725-17 725-06 02 300-04D.cdr.

[725.8] Where damage to remote-control circuits of safety control equipment would introduce a hazard [725.8(A)], provide a suitable means of protection, such as rigid metal conduit.

Class 1 Highlights

Of the three classes, this one has the tightest limitations on power levels. If you exceed those power levels, you are no longer at Class 1 and must then adhere to stricter standards of materials and installation. Here are some key points to remember:

Class 2 and Class 3

The NEC does not require you to install Class 2 and 3 in a raceway. But, if you do install them in a raceway, you should do so per the BICSI Cabling Installation Manual. This installation guideline recommends that raceway runs:

Because most installers have no idea how to limit the pulling tension on signal or communication cables, the generally accepted practice is to size the raceway so the cables do not exceed the percentage fill listed in Chapter 9, Table 1 of the NEC.

Power sources

[725.41] The power source for a Class 2 or a Class 3 circuit must be one of the following:

Wiring

Separation from Other Systems

Lightning

[725.57] Underground installations are not considered exposed to lighting. To reduce electromagnetic interference and to reduce damage from voltage surges, the practice is to ground one end of underground cables (Figure 725-33 un725-33 725-57.cdr). Where Class 2 or Class 3 circuits run overhead between buildings, they are susceptible to lightning. The conductors must maintain at least 6 ft separation from lightning conductors. You must also ground (or interrupt) the metallic sheath as close as practicable to the point of entrance. Where grounded, follow 800.40 or 820.40 as applicable.

Article 725 consists of three parts. Part I provides general information, Part II pertains to Class 1 cabling, and Part II pertains to Class 2 and 3 cabling. The key to understanding and applying each of the three parts is knowing the voltage levels of the cabling involved and the purposes of that cabling. Article 725 allows you to save time and money when working with particular types of circuits. Thus, it’s a good investment for people who work with low-power circuits to become familiar with Article 725.

Click here to view the survey results from this newsletter.

Copyright © 2002 Mike Holt Enterprises,Inc.
1-888-NEC-CODE (1-888-632-2633)