This article was posted 11/26/2013 and is most likely outdated.

Mike Holt - Article_300.22_11-26-13
header
2011 Changes to the NEC - 300.22
Based on - NEC - 2011 Edition

2011 Changes to the NEC – 300.22

The following is an instructional page from our 2011 Changes to the NEC Textbook/DVD Package complete with graphics and video where applicable. As part of our on-going effort to provide free resources to help the industry, we will be sending this content as part of a series of newsletters. Each newsletter will feature pages taken directly from our textbooks. This can be a great training resource for your organization!

There are some important features in this text which help to highlight the changes that you should be aware of:

  • Each Code section which contains a change includes a summary of the change, followed by a paraphrase of the NEC text affected by the change. Any specific change is denoted by underlined text and in the corresponding chapter color
  • Graphics with green borders and 2011 CC icons next to the heading are graphics that contain a 2011 change; graphics without a green border or icon are graphics that support the concept being discussed, but nothing in the graphic was affected by a 2011 Code change.
2011 Changes to the NEC

300.22 Wiring in Ducts and Other Spaces for Environmental Air (Plenums)

Extensive revisions have been made to the language of this section, and a new subsection was added addressing cable trays.


300.22 Wiring in Ducts Not for Air Handling, Fabricated Ducts for Environmental Air, and Other Spaces For Environmental Air (Plenums). The provisions of this section apply to the installation and uses of electrical wiring and equipment in ducts used for dust, loose stock, or vapor removal; ducts specifically fabricated for environmental air, and spaces used for environmental air (plenums).

(A) Ducts Used for Dust, Loose Stock, or Vapor. Ducts that transport dust, loose stock, or vapors must not have any wiring method installed within them. Figure 300–13

Image2

Figure 300-13

(B) Ducts Specifically Fabricated for Environmental Air. If necessary for direct action upon, or sensing of, the contained air, Type MC cable that has a smooth or corrugated impervious metal sheath without an overall nonmetallic covering, electrical metallic tubing, flexible metallic tubing, intermediate metal conduit, or rigid metal conduit without an overall nonmetallic covering can be installed in ducts specifically fabricated to transport environmental air. Flexible metal conduit in lengths not exceeding 4 ft can be used to connect physically adjustable equipment and devices within the fabricated duct.

Equipment is only permitted within the duct specifically fabricated to transport environmental air if necessary for the direct action upon, or sensing of, the contained air. Equipment, devices, and/or illumination are only permitted to be installed in the duct if necessary to facilitate maintenance and repair. Figure 300–14

Image2

Figure 300-14

(C) Other Spaces Used for Environmental Air (Plenums). This section applies to wiring and equipment in spaces not specifically fabricated for environmental air-handling purposes (plenums) but used for air-handling purposes as a plenum. This requirement doesn’t apply to habitable rooms or areas of buildings, the prime purpose of which isn’t air handling.

Note 1: The spaces above a suspended ceiling or below a raised floor used for environmental air are examples of the type of space to which this section applies. Figure 300–15

Image2

Figure 300-15

Note 2: The phrase “other space used for environmental air (plenum) ” correlates with the term “plenum” in NFPA 90A, Standard for the Installation of Air-Conditioning and Ventilating Systems, and other mechanical codes where the plenum is used for return air purposes, as well as some other air-handling spaces.

(1) Wiring Methods. Electrical metallic tubing, rigid metal conduit, intermediate metal conduit, armored cable, metal-clad cable without a nonmetallic cover, and flexible metal conduit can be installed in environmental air spaces. If accessible, surface metal raceways or metal wireways with metal covers can be installed in environmental air spaces. Figure 300–16

Image2

Figure 300-16

Author’s Comments:
•  PVC conduit [Article 352], electrical nonmetallic tubing [Article 362], liquidtight flexible conduit, and nonmetallic cables aren’t permitted to be installed in spaces used for environmental air because they give off deadly toxic fumes when burned or superheated.
•  Control, signaling, and communications cables installed in spaces used for environmental air must be suitable for plenum use. Figure 300–17

–   CATV, 820.179(A)
–   Communications, 800.21
–   Control and Signaling, 725.154(A)
–   Fire Alarm, 760.7
–   Optical Fiber Cables and Raceways, 770.113(C)
–   Sound Systems, 640.9(C) and 725.154(A)

Image2

Figure 300-17

•  Any wiring method suitable for the condition can be used in a space not used for environmental air-handling purposes. Figure 300–18

Image2

Figure 300-18

(2) Cable Tray Systems.

(a) Metal Cable Tray Systems. Metal cable tray systems can be installed to support the wiring methods and equipment permitted by this section. Figure 300–19

Image2

Figure 300-19

(3) Equipment. Electrical equipment with a metal enclosure or nonmetallic enclosures listed for use within an air-handling space (plenum) and having adequate fire-resistant and low-smoke-producing characteristics can be installed.

Author’s Comment: Dry-type transformers with a metal enclosure, rated not over 50 kVA, can be installed above suspended ceilings used for environmental air [450.13(B)]. Figure 300–20

Image2

Figure 300-20

ANALYSIS: There’s long, long been confusion about the terms “plenum” and “other space(s) used for environmental air.” While nearly all mechanical codes (NFPA 90A Standard for the Installation of Air-Conditioning and Ventilating Systems, International Mechanical Code (IMC), and Uniform Mechanical Code (UMC)) use the term “plenum” for anything that moves environmental air, the NEC only referred to a physically constructed duct as a “plenum.” The space beneath a raised floor and the space above a suspended ceiling (when used for air handling) were referred to as “other spaces used for environmental air.” Obviously the Code shouldn’t be the document that defines air system components, yet manufacturers were forced to have their product literature include provision for these “other spaces,” which created massive confusion for people installing, designing and inspecting mechanical systems. The confusion was rampant enough to require an Informational Note in the NEC trying to explain what these spaces really were! With change, a component of an air-handling system that’s created for the sole purpose of moving air (such as a duct made of tin or drywall) is now called a “duct specifically fabricated for environmental air.” The space above a ceiling or below a floor that’s used for air moving isn’t fabricated for that sole purpose and therefore isn’t a “duct,” according to mechanical codes. These spaces are now referred to as “other spaces used for environmental air (plenums),” which correlates with other codes and also has the desired effect of using commonly accepted trade language—most people refer to the space above a suspended ceiling as a “plenum ceiling,” not an “other space used for environmental air ceiling.”

Additional changes to this section include a new provision dealing with cable trays in other spaces used for environmental air (plenums), which requires these cable trays to be metallic. Solid metal cable trays with metal covers can be used to support and enclose wiring methods that traditionally weren’t allowed in these locations

 

2011 NEC Changes DVD Package
Image4

Don't let the scale of the code changes intimidate you, this package will get you up to speed on the most essential 2011 NEC changes quickly. The book is well-organized, easy to follow, and the full-color illustrations bring the material to life. The DVDs bring together a group of experts from the field to discuss the changes and how they apply in the real-world.

This program includes the following items:

  • Changes to the NEC 2011 Textbook
  • Changes to the NEC 2011 DVD 1 & 2 includes Articles 90 - 810

Product Code: 11CCDVD
Price: $198.00

Order Now

footer
This newsletter was sent to 31335 Subscribers
Unsubscribe
Comments
    No comments to display

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter