Grounding vs Bonding Online Training
 

 
Grounding vs Bonding: 250.86 Other Enclosures

March 17, 2006  

  View Comments | Add Comments | Notify Me When Comments Are Added  

PART IV. GROUNDING (BONDING) OF ENCLOSURE, RACEWAY, AND SERVICE CABLE   Hi Res - Cable/DSL [1249Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
      
Sections

250.86 Other Enclosures.

Metal raceways and enclosures containing electrical conductors that operate at over 50V [250.112(I)] must be grounded (bonded) to an effective ground-fault current path [250.4(A)(5)].

Author’s Comment: Metal raceways and metal enclosures containing circuit conductors from electrical supply sources that operate at 50V or less aren’t required to be grounded [250.86]. For example, metal boxes used with power-limited fire alarm circuits operating at 50V or less aren’t required to be grounded.
Exception 2: Short sections of metal raceways used for the support or physical protection of cables aren’t required to be grounded (bonded) to an effective ground-fault current path. Figure 250–123

Author’s Comment: NM cable on a wall of an unfinished basement installed, in a listed metal raceway, must be grounded to an effective ground-fault current path [334.15(C)].
Exception 3: Metal elbows having 18 in. or more of earth cover aren’t required to be grounded (bonded) to an effective ground-fault current path. Figure 250–124



Figure 250–123
(Click on image to enlarge)


Figure 250–124
(Click on image to enlarge)

     

Copyright © 2005 Mike Holt Enterprises,Inc.
1-888-NEC-CODE (1-888-632-2633)

 

Comments

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter