This article was posted 04/14/2006 and is most likely outdated.

Grounding vs Bonding Online Training
 

 
Grounding vs Bonding: 250.94 Grounding (Bonding) of Communications Systems

April 14, 2006  

  View Comments | Add Comments | Notify Me When Comments Are Added  

PART V. BONDING   Hi Res - Cable/DSL [5739Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]

Sections

250.94 Grounding (Bonding) of Communications Systems.

An accessible bonding point must be provided at service equipment or the disconnecting means of separate buildings or structures for communications systems. The point can be any one of the following:

(1) An exposed, nonflexible metallic raceway.
(2) An exposed grounding electrode conductor.
(3) An external connection approved by the authority having jurisdiction.

FPN No. 2: Communications systems must be bonded together. Figure 250–134

• Antennas/Satellite Dishes, 810.21
• CATV, 820.100
• Telephone Circuits, 800.100

Author’s Comment: The bonding of all external communications systems to a single point minimizes the possibility of damage to the systems from potential (voltage) differences between the systems. Figure 250–135


 

imageSend to a Friend


Figure 250–134
(Click on image to enlarge)


Figure 250–135
(Click on image to enlarge)

     

Copyright © 2006 Mike Holt Enterprises,Inc.
1-888-NEC-CODE (1-888-632-2633)

 

Comments

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter