Visit MikeHolt.com
NEC Questions and Answers - June 2016  

 
Image

By Mike Holt for EC&M Magazine

Here's the follow up to yesterday's newsletter. This includes all of the answers to the questions sent, so you can see how you did.

Note: These questions are based on the 2014 NEC.

 

Q1. Where does the Code require Arc-Fault Circuit-Interrupter Protection?

A1. Arc-fault circuit-interrupter protection must be provided in accordance with 210.12(A), (B) and (C). AFCI devices must be installed in readily accessible locations [210.12].

All 15A or 20A, 120V branch circuits in dwelling units supplying outlets or devices in kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways, laundry areas, or similar rooms or areas must be protected by one of the following [210.12(A)] :

(1) A listed combination type AFCI, installed to provide protection of the entire branch circuit.

(2) A listed branch/feeder type AFCI at the origin of the branch circuit, plus a listed outlet branch-circuit AFCI installed at the first outlet box of the branch circuit. The outlet box must be marked to indicate that it’s the first outlet box of the circuit.

(3) A listed supplemental arc protection circuit breaker installed at the origin of the branch circuit, plus a listed outlet branch-circuit type AFCI installed at the first outlet box on the branch circuit. When using this option, the following must be met:
(a) The branch-circuit wiring must be continuous from the branch circuit overcurrent device to the AFCI device.
(b) The maximum length of the branch circuit to the AFCI is 50 ft for 14 AWG conductors or 70 ft for 12 AWG conductors.
(c) The first outlet box in the circuit must be marked.

(4) A regular fuse or circuit breaker, plus a listed outlet branch-circuit type AFCI installed at the first outlet of the branch circuit. When using this option, the following must be met:
(a) The branch-circuit wiring must be continuous from the branch-circuit overcurrent device to the AFCI device.
(b) The maximum length of the branch circuit to the AFCI is 50 ft for 14 AWG conductors or 70 ft for 12 AWG conductors.
(c) The first outlet box in the circuit must be marked.
(d) The combination of the branch-circuit overcurrent device and the AFCI must be listed and identified as meeting the requirements for a “System Combination” type AFCI.

(5) A listed outlet branch-circuit type AFCI at the first outlet can be used, if the wiring between the overcurrent device and the AFCI contains all metal boxes and is installed using any (or a combination) of the following: RMC, IMC, EMT, Type MC, Type AC cables meeting the requirements of 250.118, metal wireways, or metal auxiliary gutters.

(6) A listed outlet branch-circuit type AFCI at the first outlet of the circuit can be used, if the wiring between the overcurrent device and the AFCI is in a raceway with 2 in. of concrete encasement.

Author’s Comment:
The combination AFCI is a circuit breaker that protects downstream branch-circuit wiring as well as cord sets and power-supply cords; an outlet branch-circuit AFCI (receptacle) is installed as the first outlet in a branch circuit to protect downstream branch-circuit wiring, cord sets, and power-supply cords.

The 120V circuit limitation means AFCI protection isn’t required for equipment rated 230V, such as a baseboard heater or room air conditioner. For more information, visit www.MikeHolt.com, click on the “Search” link, and then search for “AFCI.”

Ex: AFCI protection can be omitted for an individual branch circuit to a fire alarm system in accordance with 760.41(B) and 760.121(B), if the circuit conductors are installed in metal wireways, metal auxiliary gutters, RMC, IMC, EMT, or steel sheath Type AC or MC cable that qualifies as an equipment grounding conductor in accordance with 250.118, with metal outlet and junction boxes.

Informational Note 3: See 760.41(B) and 760.121(B) for power-supply requirements for fire alarm systems.

Author’s Comment:
Smoke alarms connected to a 15A or 20A circuit in a dwelling unit must be AFCI protected if the smoke alarm is located in one of the areas specified in 210.12(A). The exemption from AFCI protection for the “fire alarm circuit” contained in 760.41(B) and 760.121(B) doesn’t apply to the single- or multiple-station smoke alarm circuit typically installed in dwelling unit bedroom areas. This is because a smoke alarm circuit isn’t a fire alarm circuit as defined in NFPA 72, National Fire Alarm Code. Unlike single- or multiple-station smoke alarms, fire alarm systems are managed by a fire alarm control panel.

(B) Branch-Circuit Extensions or Modifications—Dwelling Units. Where branch-circuit wiring is modified, replaced, or extended in any of the areas specified in 210.12(A), the branch circuit must be protected by:

(1) A listed combination AFCI located at the origin of the branch circuit; or

(2) A listed outlet branch circuit AFCI located at the first receptacle outlet of the existing branch circuit.

Ex: AFCI protection isn’t required for extensions less than 6 ft long, as long as there are no outlets or devices added.

(C) Dormitory Units. All 120V, single phase, 15A and 20A branch circuits supplying outlets installed in dormitory unit bedrooms, living rooms, hallways, closets, and similar rooms must be AFCI protected by one of the methods discussed in 210.12(A)(1) through (6).

 

Q2. What is the Code requirement for outlets that supply electric vehicle chargers?

A2. Electric vehicle charging outlets must be supplied by a circuit that has no other outlets [210.17].
Author’s Comment: See 625.2 for the definition of “Electrical Vehicle.”

 

Q3. Are guest rooms and guest suites required to follow the same branch circuit requirements as dwelling units?

A3. Guest rooms and guest suites provided with permanent provisions for cooking must have branch circuits installed in accordance with the dwelling unit requirements of Article 210 [210.18].

Author’s Comment:
See the definitions of “Guest Room” and “Guest Suite” in Article 100.

 

Click Here to Post a Comment Click Here to View Comments Click Here to Unsubscribe
 
 
Visit: Exam Preparation | Continuing Education | Code Products | Newsletters | and more
Copyright© Mike Holt Enterprises of Leesburg, Inc. All Rights Reserved This article is protected by United States copyright laws and may not be published without prior written permission.
Mike Holt Enterprises of Leesburg, Inc. 3604 Parkway Blvd. Suite 3 Leesburg, FL 34748
"... as for me and my house, we will serve the Lord." [Joshua 24:15]
Comments
  • Since lighting is also integral to General purpose receptacle branch circuits, would not the entire dwelling with exception of 240v circuits be AFCI protected under the AFCI code?

    Mark Michael  July 8 2016, 4:38 pm EDT
    Reply to this comment

  • Where do circa 1958 vintage houses fall with all this? All Power comes through fused disconnects, Fuse Panels, etc.in a partial Basement 7ft. I just updated my 2-wire house with GFCI's for my Safety sake. 1. What else would be required to replace Fuse Panel with CB Panel 2. Has anyone ever heard of mounting a CB Panel Horizontally due to height constraint in Partial Basement?

    Bill  June 24 2016, 4:05 pm EDT
    Reply to this comment

  • As briefly as possible, what receptacles must be AFI protectected and/or, what receptacles do not require AFI protection?

    How different will a breaker panel look that meets these standards?

    Are there combination AFCIs and GFCIs?

    What is an estimated additional cost for AFI protection in a 2000 sf home with garage, new construction?

    If the cost to implement is significant, what is the justification in lives and/or value of property?

    Ken  June 23 2016, 5:08 am EDT
    Reply to this comment

  • From what I read, outside lights and receptacles are not required to have AFCI protection. Am I reading this correct?

    Jeff  June 22 2016, 9:57 pm EDT
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter