Mike Holt Enterprises Electrical News Source

NEC Questions and Answers based on 2017 NEC® - June 2019

Figure 01

For EC&M Magazine
By Mike Holt, NEC® Consultant
Here's the follow-up to yesterday's newsletter. This includes the answers to the questions sent, so you can see how you did.

Note: The answers to these questions are based on the 2017 NEC.

Q1. How does the NEC define a Cable Tray System?
A1. A cable tray system is a unit or assembly of units or sections with associated fittings forming a rigid structural system used to securely fasten or support cables, raceways, and boxes [392.2]. Figure 01

Author’s Comment:

  • Cable tray isn’t a type of raceway. It’s a support system for cables and raceways.

Q2. What are the Code permitted uses of a Cable tray?
A2. Cable trays can be used as a support system for service, feeder, or branch-circuit conductors, as well as communications circuits, control circuits, and signaling circuits [392.10]. Cable tray installations aren’t limited to industrial establishments. If exposed to the direct rays of the sun, insulated conductors and jacketed cables must be identified as being sunlight resistant. The manufacturer must identify cable trays and associated fittings for their intended use.

Author’s Comment:

  • Cable trays used to support service-entrance conductors must contain only service-entrance conductors unless a solid fixed barrier separates the service-entrance conductors from other conductors [230.44].

Q3. What wiring methods does the NEC allow to be installed in a cable tray?
A3. Any wiring methods listed in Table 392.10(A) can be installed in a cable tray [392.10(A)].

Author’s Comment:

  • Control, signal, and communications cables must be separated from the power conductors by a barrier or maintain a 2-in. separation.
  • Coaxial Cables, 820.133(A)(1)(b) Ex 1
  • Class 2 and 3 Cables, 725.136(B) and 725.136(I)
  • Communications Cables, 800.133(A)(2) Ex 1
  • Fire Alarm Cables, 760.136(G)
  • Optical Fiber Cables, 770.133(B)
  • Intrinsically Safe Systems Cables, 504.30(A)(2) Ex 1
  • Radio and Television Cables, 810.18(B) Ex 1

Table 392.10(A) Wiring Methods

Wiring Method

Article/Section

Armored cable

320

Coaxial cables

820

Class 2 & 3 cables

725

Communications cables

800

Communications raceways

725, 770, and 800

Electrical metallic tubing

358

Electrical nonmetallic tubing

362

Fire alarm cables

760

Flexible metal conduit

348

Instrumentation tray cable

727

Intermediate metal conduit

342

Liquidtight flexible metal conduit

350

Liquidtight flexible nonmetallic conduit

356

Metal-clad cable

330

Nonmetallic-sheathed cable

334

Nonpower-limited fire alarm cable

760

Polyvinyl chloride (PVC) conduit

352

Power and control tray cable

336

Power-limited fire alarm cable

760

Power-limited tray cable

Table 725.154 and 725.179(E) and 725.71(F)

Rigid metal conduit

344

Service-entrance cable

338

Signaling raceway

725

Underground feeder and branch-circuit cable

340

For uses permitted in industrial establishments [392.10(B):
Where conditions of maintenance and supervision ensure that only qualified persons service the installed cable tray system, single-conductor cables can be installed if:

  • 1/0 AWG and larger listed and marked for use in cable trays [392.10(B)(1)(a)].
  • Equipment grounding conductors must be 4 AWG and larger [392.10(B)(1)(c)].

Cable trays in hazardous locations must contain only the cable types and raceways permitted by the Code for the application [392.10(C)].

Author’s Comment:

  • For permitted cable types, see 501.10, 502.10, 503.10, 504.20, and 505.15.
In addition to the uses permitted elsewhere in Article 392, nonmetallic cable trays can be installed in corrosive areas, and in areas requiring voltage isolation [392.10(D)].

Q4. What uses of cable trays are not permitted by the NEC?
A4. Cable tray systems aren’t permitted in hoistways, or where subject to severe physical damage [392.12].

Q5. What is the NEC rule regarding the continuity of cable tray systems and their accessibility?
A5. Cable trays must be installed as a complete system, except mechanically discontinuous segments between cable tray runs, or between cable tray runs and equipment are permitted. The system must provide for the support of the cables and raceways in accordance with their corresponding articles [392.18].

A bonding jumper, sized in accordance with 250.102 and installed in accordance with 250.96, must bond the sections of metal cable tray, or the cable tray and the raceway or equipment.

Each run of cable tray must be completed before the installation of cables or conductors [392.18(B)].

Cable trays can extend through partitions and walls, or vertically through platforms and floors if the installation is made in accordance with the firestopping requirements of 300.21 [392.18(D)].

Cable trays must be exposed and accessible, except as permitted by 392.18(D) [392.18(E)].
Sufficient space must be provided and maintained about cable trays to permit adequate access for installing and maintaining the cables [392.18(F)].

Comments
  • I've taken the TN state exam twice and failed. I'm real discouraged.

    Dwayne Bryant  September 6 2019, 1:18 pm EDT
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter