Mike Holt Enterprises Electrical News Source

Flexible Cords and Flexible Cables, based on the 2020 NEC®

Figure 01

For EC&M Magazine
By Mike Holt, NEC® Consultant

Note: This article is based on the 2020 NEC.

The rules for using flexible cords and flexible cables are more involved than many people believe.

Article 400 covers the general requirements, applications, and construction specifications for flexible cords and flexible cables. You can get a sense of the sheer variety of them, and their applications, from Table 400.4.

Why is this not Article 3xx? Why is it in Chapter 4, instead of Chapter 3? The NEC does not consider flexible cords to be a wiring method like those addressed in Chapter 3. Unlike wiring methods, flexible cords and flexible cables are not affixed to a surface. And you don’t install them in the sense you install a Chapter 3 wiring method.

They may, however, be used in a building to connect equipment to a permanent power source. Luminaires and sump pump motors are two examples of this type of use. The former permits easy configuration changes, the latter accommodates vibration.

You don’t run flexible cords and flexible cables in raceway, though you may use cord guards or other devices such as cable looms to protect them from mechanical damage and (where run near walkways) to prevent them from presenting a tripping hazard.

While these cords and cables are manufactured to standards that make them safe to use, they are considered safe to use only when identified for the use and the application. So always use the flexible cord (and fittings) that’s right for the job.

For example, use cords listed for a wet location if you are using them outdoors. The jacket material of a flexible cord is tested to maintain its insulation properties and other characteristics in the environments for which it has been listed. It may seem logical that any cord jacket is suitable for wet conditions, after all it’s some sort of plastic. Yes, any jacket used today will probably keep water out under normal use. But has it been tested to keep electricity in while it’s wet? Or after it’s baked in the hot sun for a few weeks? The suffix “W” at the end of a flexible cord type designates that the flexible cord is water and sunlight resistant [Table 400.4, Note 9].

Table 400.4 will help you identify whether a given type of cord or cable fits your intended application. Though it’s a monster table that runs several pages, its arrangement is based on the Type Letter. Those are in alphabetical order starting with C and ending with W. The Type Letter is the second column, not the first column, which is a little confusing at first glance.

Ampacity
You need to use a cord that has suitable ampacity for the application. Tables 400.5(A)(1) and 400.5(A)(2) are important tables to turn to when looking for the ampacity of flexible cords and cables. These cords and cables include various types of wire which might be used for lamps, appliances, extension cords, drop and pendant lights, pool pumps, and so on.

Table 400.5(A)(1) lists the ampacity for the individual conductors inside manufactured flexible cords. Table 400.5(A)(2) lists the ampacity for overall cord assemblies with not more than three current-carrying conductors in an ambient temperature of not more than 86 DegrF.

Ordering cords
If you need to order cord for a project, be specific. What you ask for is exactly what you get. It’s not like ordering a wiring method.

For example, consider this common wiring method: 14/2 Nonmetallic Sheathed Cable (NMC) [Article 334]. It has a black conductor, a white conductor, and an equipment grounding conductor. But 14/2 SJ cord will have only two conductors and no equipment ground. 14/3 SJ has three conductors including the equipment ground. So be sure to order by the total number of conductors needed for your installation.

Uses permitted
So where can you use flexible cords and flexible cables? Within the scope of this article, they can be used for [400.10(A)]:

(1) Pendants [receptacles—210.50(A) and boxes—314.23(H)].

(2) Wiring of luminaires [410.24(A) and 410.62(B)]. Note that you don’t use flexible cords inside ceiling areas or other hidden places, because rodents can chew through the insulation. In those locations, you must use something the little critters can’t chew through. If you still want that flexibility because you might move the light fixture, then something like Type AC Cable [Article 320] works well. In fact, you can buy “fixture whips” specifically for this purpose.

(3) Connection of portable luminaires, portable and mobile signs, or appliances [422.16].

(4) Elevator cables.

(5) Wiring of cranes and hoists.

(6) Connection of utilization equipment to facilitate frequent interchange [422.16].

(7) Prevention of the transmission of noise or vibration [422.16].

(8) Appliances where the fastening means and mechanical connections are specifically designed to permit ready removal for maintenance and repair, and the appliance is intended or identified for flexible cord connections [422.16]. Note that water heaters, furnaces, and other appliances fastened in place cannot be connected with a flexible cord unless the appliances are specifically identified to be used with a flexible cord [422.16(A)(2)].

(9) Connection of moving parts.

(B) Attachment plugs are required for flexible cords used in any of the following applications:

  • Portable luminaires, portable and mobile signs, or appliances [400.10(A)(3)].
  • Stationary equipment to facilitate its frequent interchange [400.10(A)(6) and 422.16(A)(1)].
  • Appliances specifically designed to permit ready removal for maintenance and repair and identified for flexible cord connection [400.10(A)(8)].

Uses not permitted
You can’t use flexible cords and cables in place of a Chapter 3 wiring method for fixed wiring, though some people try. Sometimes, it’s taken to extremes. To avoid running raceway and conductors for about 400A of 480V power to a new production room, maintenance personnel at a Tennessee appliance plant bundled a large number of Type SO flexible cords with tie wraps into a collection of cord bundles (10 cords per bundle). They even hung the resulting bundle of bundles from raceway, cable tray, and building structural members (I-beams).

Their “reasoning” for this approach was that since flexible cord was used for overhead fluorescent fixtures, it must be just as good as wire run in raceway. Regardless of distance or density. And none of them knew how to run raceway.
While this was an impressive feat of cable-wrapping, it presented a significant fire hazard. The newly hired plant engineer, who was an industrial engineer rather than an electrical one, took one look at this and contacted an electrical contractor to replace it with “something Code compliant.” He then set about hiring actual electricians into maintenance, specifically telling HR that the applicants must have skill in running raceway and pulling wire. It’s really too bad that plant engineer didn’t take photos to submit to EC&M for the Code Violations column.

Unless specifically permitted in 400.10, flexible cords, flexible cables, cord sets (extension cords), and power-supply cords are not permitted to be [400.12]:
(1) Substitutes for the fixed wiring (as just discussed).

(2) Run through holes in walls, structural ceilings, suspended or dropped ceilings, or floors. Figure 01

(3) Run through doorways, windows, or similar openings.

(4) Attached to building surfaces.

(5) Concealed by walls, floors, or ceilings, or located above suspended or dropped ceilings.

Ex to (5): Flexible cords, flexible cables, and power-supply cords are permitted if contained within an enclosure for use in other spaces used for environmental air as permitted by [300.22(C)(3)].

(6) Installed in raceways, except as permitted by 400.17 for industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons will service the installation.

(7) Installed where they are subject to physical damage, or installed in such a way as to subject them to physical damage.

Pull at joints and terminals
Flexible cords must be installed so tension will not be transmitted to the conductor terminals [400.14]. This can be accomplished by knotting the cord, winding the flexible cord with tape, or using support or strain-relief fittings.

Protection from damage
Flexible cords must be protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures [400.17]. Commercial products also exist to protect cords from many other types of damage. But sometimes, the best option is to use a flexible Chapter 3 wiring method.

Staying compliant
The biggest mistake made with flexible cords and flexible cables is using the wrong one for the application. To prevent this, use Table 400.4 to select the right Letter Type and Tables 400.5(A)(1), (2), and (3) to select the correct ampacity. To keep the installation safe, ensure each cable or cord is installed in a manner that protects it from mechanical damage.

Comments
    No comments to display

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter