Has anyone had trouble with Arc Fault brkrs self tripping after they are a year old +? These brkrs are installed in 3r panel on the outside of modified trailer dwellings. After trouble shooting said defective brkrs I found out that the brkr is sending 120v through its neutral wire to the neutral buss bar causing the self tipping. Has anyone else had this happen to them. These brkrs are made by Cutler Hammer and are type BRAF. Any info would be greatly appreciated. Michael Tallon
will please inform me what the code say about emergency panel in same closet with normal power.thank