This article was posted 06/29/2007 and is most likely outdated.

Article 410 Luminaires (Lighting Fixtures), Lampholders, and Lamps - 410.73
 

 
Subject - Article 410 Luminaires (Lighting Fixtures), Lampholders, and Lamps - 410.73
Based on - NEC - 2005 Edition

June 29, 2007
This newsletter was sent to 26226 newsletter subscribers
 

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 410   Hi Res - Cable/DSL [15688Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
    
Luminaires (Lighting Fixtures), Lampholders, and Lamps

410.73 General

Part XIII. Electric-Discharge Lighting (1,000V or Less)

New rule specifies when luminaires with metal halide lamp are to be provided with a method to help contain the arc at end-of-life arc-tube failures.

(F) High-Intensity Discharge Luminaires.
(5) Metal Halide Lamp Containment. Luminaires containing metal halide lamp, other than a thick-glass parabolic reflector lamp (PAR), must be provided with a containment barrier that encloses the lamp or the luminaire must only allow the use of a Type “O” lamp.
Figure 410-7

Author’s Comment: Fires have resulted from the spillage of hot arc tube particles from metal halide lamp failures. “O-rated” lamps have been designed to meet ANSI containment test for the installation of the metal halide lamp in an open fixture.



Figure 410-7
(Click on image to enlarge)

       
 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

Comments
  • All non-enclosed Metal Halide lumineres must have a "Pink" socket to distiguish the socket using the proper lamp.

    John Turilli
    Reply to this comment

  • is there a code that will let you put a white wire on a breaker

    dale l dascher
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter