Article 320 Armored Cable: Type AC
 

 
Subject - Article 320 Armored Cable: Type AC

March 9, 2007  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 320   Hi Res - Cable/DSL [18027Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
    
Armored Cable: Type AC

320.30 Secured and Supported

Part II. Installation

This section was reorganized with editorial changes to add clarity and uniform interpretation. New subsection (A) General, gives a title to the opening paragraph and includes requirements that apply generally. The requirements for securing and supporting have been separated into (B) and (C), as they are two different issues.
(A) General. Type AC cable must be supported and secured by staples, cable ties, straps, hangers, or similar fittings, designed and installed not to damage the cable.

(B) Securing. Type AC cable must be secured within 12 in. of every outlet box, junction box, cabinet, or fitting and at intervals not exceeding 4 1/2 ft where installed on or across framing members. Figure 320-1

Author’s Comment: Type AC cable is considered secured when installed horizontally through wooden or metal framing members [320.30(C)].

(C) Supporting. Type AC cable must be supported at intervals not exceeding 4 1/2 ft. Cables installed horizontally through wooden or metal framing members are considered secured and supported where such support doesn’t exceed 41/2 ft intervals. Figure 320-2

(D) Unsupported Cables. Type AC cable can be unsupported where the cable is:
(1) Fished through concealed spaces in finished buildings or structures, where support is impracticable; or
(2) Not more than 2 ft long at terminals where flexibility is necessary; or
(3) Not more than 6 ft long from the last point of cable support to the point of connection to a luminaire or other piece of electrical equipment within an accessible ceiling.

For the purposes of this section, Type AC cable fittings are permitted as a means of cable support.
Figure 320-3


Figure 320-1
(Click on image to enlarge)


Figure 320-2
(Click on image to enlarge)


Figure 320-3
(Click on image to enlarge)

   
 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

Comments
  • I have had this argument with insectors for years. It is good to have it brought out in the open like this. I also liked the option of watching Mike tell us about it via the internet. Thanks Mike.

    ROBERT DEMOTT

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter