Online Video

Back to Video Menu  
Illustrated Changes to the NEC, 2002 Edition - Part 2

Article 640

Audio Signal Processing, Amplification, And Reproduction Equipment

640.6 Mechanical Execution of Work/Cable Support

The text to this section was revised to read:

Equipment and cabling must be installed in a neat and workmanlike manner. Cables installed exposed on the surface of ceilings and sidewalls must be supported by the structural components of the building in such a manner that the cable will not be damaged by normal building use. Such cables must be secured to structural components by straps, staples, hangers or similar fittings designed and installed so as not to damage the cable. Figure 640-1

Cables installed parallel to framing members must be protected against physical damage from penetration by screws or nails by 1.25 in. separation from the framing member or by a suitable metal plate in accordance with 300.4(D). Figure 640-2
Intent: The revised text clarifies that cables must be properly secured and protected from physical damage.


VIEW VIDEO ( Click on your connection speed to view )
[ Modem/Dial-up ]   [ Cable/DSN ]  
REQUIRES

[ FREE ]
If you have already been approved for reprint permission, you may right mouse click on the link above and choose "Save Target As ..." or "Save Link As ..." to save the file to your local computer.
©2005 Mike Holt Enterprises, Inc.