Grounding versus Bonding

PART III. GROUNDING ELECTRODE SYSTEM AND GROUNDING ELECTRODE CONDUCTOR

Sections

250.58 Common Grounding (Earthing) Electrode.

Where a building or structure is supplied with multiple services or feeders as permitted by 225.30 and 230.2, the same electrode must be used to ground enclosures and equipment in or on that building.

Author’s Comments:
• Metal parts of the electrical installation are grounded to the earth to reduce voltage on the metal parts from lightning so as to prevent fires from a surface arc within the building or structure. Grounding electrical equipment to earth doesn’t serve the purpose of providing a low-impedance fault-current path to clear ground faults.
• The most practical method of meeting this requirement is to ground each of the disconnecting means to a common concrete-encased grounding electrode [250.52(A)(3)]. Figure 250–108

CAUTION: Potentially dangerous objectionable current flows on the grounding electrode conductor when multiple service disconnecting means are grounded to the same electrode. This is because neutral current from each service can return to the utility via the common grounding electrode and its conductors. This is especially a problem if one of the grounded neutral service conductors is opened. Figure 250–109