Grounding versus Bonding

PART III. GROUNDING ELECTRODE SYSTEM AND GROUNDING ELECTRODE CONDUCTOR

Sections

250.68 Grounding Electrode Conductor Termination.

(A) Attachment Fitting. The grounding electrode attachment fitting must be accessible.

Exception 1: The grounding electrode attachment fitting to an encased or buried grounding electrode isn’t required to be accessible. Figure 250–119

Author’s Comment: When the grounding electrode attachment fitting is encased in concrete or buried, it must be listed and identified for this purpose [250.70].
Exception 2: An exothermic or irreversible compression connection to fireproofed structural metal isn’t required to be accessible.

(B) Effective Ground-Fault Current Path. To ensure a permanent and effective grounding path for an underground metal water pipe electrode, a bonding jumper must be installed around insulated joints and equipment likely to be disconnected for repairs or replacement. Figure 250–120

Author’s Comment: Continuity of the conductive bonding path for metal water piping as required by 250.104(A) cannot rely on water meters, filtering devices, or similar equipment [250.53(D)(1)].