Grounding versus Bonding

PART II.

Sections

250.32 Buildings or Structures Supplied by a Feeder or Branch Circuit Continued

The equipment grounding (bonding) conductor, if of the wire type, must be sized in accordance with 250.122, based on the rating of the feeder protection device.

CAUTION: To prevent dangerous objectionable current from flowing onto metal parts of the electrical installation, as well as metal piping and structural steel [250.6(A)], a building or structure disconnecting means supplied by a feeder must not have the grounded neutral conductor bonded to the building or structure disconnecting means. Figures 250Ė85 and 250Ė86
(2) Grounded Neutral Conductor. When an equipment grounding (bonding) conductor is not run to the building or structure disconnecting means, the building or structure disconnecting means can be bonded to a grounded neutral conductor installed with the feeder conductors. This is only permitted where thereís no continuous metallic path between buildings and structures, and ground-fault protection of equipment isnít installed on the supply side of the feeder.

Where the grounded neutral feeder conductor serves as the effective ground-fault current path, it must be sized no smaller than the larger of:

(1) The maximum unbalanced neutral load in accordance with 220.61.

(2) The available fault current in
accordance with 250.122.

CAUTION: Using the grounded neutral conductor as the effective ground-fault current path poses potentially dangerous consequences and should only be done after careful consideration. Even if the initial installation doesnít result in dangerous objectionable current on metal parts, there remains the possibility that a future installation of metal piping or cables between the buildings or structures could create unwanted parallel neutral current paths.

Authorís Comment: The preferred practice (or at least my preferred practice) is to not use the grounded neutral conductor as the effective ground-fault current path, but to install an equipment grounding (bonding) conductor with the feeder conductors to the building or structure in accordance with 250.32(B)(1).
(E) Grounding Electrode Conductor. The grounding electrode conductor for a separate building or structure disconnecting means must terminate to the grounding terminal of the disconnecting means and it must be sized in accordance with 250.66, based on the largest ungrounded feeder conductor.

Question: What size grounding electrode conductor is required for a building disconnect that is supplied with 3/0 AWG? Figure 250Ė87

(a) 4 AWG    (b) 3 AWG    (c) 2 AWG    (d) 1 AWG

Answer: (a) 4 AWG, Table 250.66

Authorís Comment: Where the grounding electrode conductor is connected to a ground rod, that portion of the conductor that is the sole connection to the ground rod isnít required to be larger than 6 AWG copper [250.66(A)]. Where the grounding electrode conductor is connected to a concrete-encased electrode, that portion of the conductor that is the sole connection to the concrete-encased electrode isnít required to be larger than 4 AWG copper [250.66(B)].