Conductor Sizing, Part 2 - based on the 2014 NEC®    

 

In case you missed it, you can click here to view Conductor Sizing, Part 1.

 

By Mike Holt, NEC Consultant

I In Part 1 we learned the correct sizing of conductors is more complicated than it appears. One reason is the way temperature affects the resistance of a conductor. A higher temperature means less current-carrying capacity for a given size conductor. With Part 1 complete, you’re now ready to select the minimum conductor size from the table. There is a catch: you can’t use a column with a temperature that exceeds the temperature rating of any device in a given run in accordance with 110.14(C)(1).

 

Branch-circuits

The ampacity of branch-circuit conductors must be at least the maximum load to be served [210.19(A)(1)]. So size the conductors to carry the larger of:

1. 125 percent of the continuous loads, plus 100 percent of the noncontinuous loads, based on the terminal temperature rating ampacities as listed in Table 310.15(B)(16); or

2. The load after the application of correction or adjustment factors.

Question: What’s the minimum size branch circuit conductor (THHN) for a 45A continuous nonlinear load that requires three ungrounded conductors and a neutral (four current-carrying conductors)?

(a) 8 AWG      (b) 6 AWG      (c) 4 AWG      (d) none of these

Answer: (c) 4 AWG.

Here are the key points for solving this problem:

  • Step 1a. Since the load is 45A continuous, the conductor must have an ampacity of at least 56A (45A x 1.25) [210.19(A)(1)(a)] before the application of any ampacity adjustment or correction.
  • Step 1a. 4 AWG is rated 70A at 60ºC on Table 310.15(B)(16), so it is suitable to meet the 56A requirement of 210.19(A)(1)(a) and the terminal requirements of 110.14(C)(1); before applying conductor ampacity adjustment and/or correction.
  • Step 2a. Because the neutral is a current-carrying conductor per 310.15(B)(5)(c), you must apply Table 310.15(B)(3) adjustment factor of 80% [210.19(A)(1)(b)].
  • Step 2b. 4 THHN has an ampacity of 95A at 90ºC [Table 310.15(B)(16)].
  • Step 2c. Adjustment factor for four current-carrying conductors is 0.80 of the ampacity of the conductor in accordance with the 90ºC insulation rating of the conductor, not the 60ºC equipment terminal rating [310.15(B) and Table 310.15(B)(3)(a)].
  • Step 2d. Adjusted Ampacity = 95A x 0.80 = 76A. The conductor after adjustment is rated 76A which is adequate for the 45A load.

 

Feeders

The ampacity of feeder conductors must be sized to carry at least the maximum load to be served [215.2(A)(1)]. So size the conductors to carry the larger of 215.2(A)(1)(a) or (b):

(c) 125 percent of the continuous loads, plus 100 percent of the noncontinuous loads, based on the terminal temperature rating ampacities as listed in Table 310.15(B)(16); or

(d) The load after the application of correction or adjustment factors.

 

Taps

Feeders bring another twist to conductor sizing: feeder tap rules. A tap is a conductor (other than a service conductor) with overcurrent protection rated higher than normally allowed in 240.2.

You can run feeder taps without overcurrent protection (at the tap location), up to 10 ft. But only if the ampacity of the tap conductor is at least the:

1. Calculated load per Article 220, and

2. Rating of the device or OCPD supplied by the tap conductors.

Also, the tap conductors must:

1. Not extend beyond the equipment they supply.

2. Be in a raceway, if they leave the enclosure,

3. Have an ampacity at least one-tenth of the rating of the OCPD that protects the feeder.

Question: Using the 10-foot tap rule, what’s the minimum size conductor you need to supply a 200A OCPD, if the tap is from feeder conductors protected by a 400A OCPD?

(a) 3 AWG     (b) 1/0 AWG      (c) 3/0 AWG      (d) 250 kcmil

Answer: (c) 3/0 AWG

The ampacity of the tap conductors must be at least the rating of:

• The 200A OCPD they terminate into, and

• One-tenth the rating of the OCPD protecting the feeder conductors.

A 3/0 AWG conductor:

• Is rated 200A at 75ºC, and

• Has an ampacity of at least 40A (one-tenth the rating of the 400A feeder OCPD (400/10) [Table 310.15(B)(16)].

What if you need a longer tap? If you don’t need to go more than 25 ft, you’re in luck [240.21(B)(2)]. However, you must satisfy three requirements to get that additional 15 ft.:

1. The ampacity of the tap conductors must be at least one-third the rating of the OCPD that protects the feeder.

2. The tap conductors must terminate in a single circuit breaker (or set of fuses) rated no more than the tap conductor ampacity per 310.15 [Table 310.15(B)(16)].

3. The tap conductors must be protected from physical damage by being enclosed in a manner approved by the authority having jurisdiction (e.g., within a raceway).

Question: Using the 25-foot tap rule, what’s the minimum size conductor to supply a 200A OCPD, if the tap is from feeder conductors protected by a 400A circuit?

(a) 3 AWG      (b) 1/0 AWG      (c) 3/0 AWG      (d) 250 kcmil

Answer: (c) 3/0 AWG

The tap conductors must have an ampacity of at least the 200A rating of the OCPD they terminate into and at least one-third the rating of the OCPD protecting the feeder conductors. A 3/0 AWG conductor is rated 200A at 75ºC and has an ampacity of at least 133A (one-third the rating of the 400A feeder OCPD (400/3) [Table 310.15(B)(16)].

 

The great outdoors

And just when you thought the feeder conductor fun was over, we have one more twist to talk about. The good news is there’s no limit on how long an outside feeder-tap can be without overcurrent protection at the point it receives its supply [240.21(B)(5)]. But only if:

1. The tap conductors are suitably protected from physical damage in a raceway or manner approved by the authority having jurisdiction.

2. The tap conductors terminate at a single circuit breaker (or single set of fuses) that limits the load to the ampacity of the conductors.

3. The OCPD for the tap conductors is an integral part of the disconnecting means, or is located immediately adjacent to it.

4. The disconnecting means is at a readily accessible location (either outside the building), or nearest the point of entry of the conductors.

 

Branch vs. Feeder

It can be hard to remember whether you size the OCPD first for branch-circuits or for feeders. The rules differ because each type of circuit serves a different purpose, but that fact alone may not help you keep things straight.

Perhaps another way of looking at it will help. The conductors of a branch-circuit must be big enough to supply the branch-circuit loads. But the conductors of a feeder circuit must be big enough to serve the feeder OCPD.

 

In case you missed it, you can click here to view Conductor Sizing, Part 1.

Click Here to Post a Comment Click Here to View Comments Click Here to Unsubscribe
 

Image

 
Visit: Exam Preparation | Continuing Education | Code Products | Newsletters | and more
Copyright© Mike Holt Enterprises of Leesburg, Inc. All Rights Reserved This article is protected by United States copyright laws and may not be published without prior written permission.
"... as for me and my house, we will serve the Lord" [Joshua 24:15]
 
Comments
  • In the key points should it reference the 90 degree column just after the table?

    Why do you not apply the correction factor to the 70A rating of the conductor under the 60 degree column?

    And if I needed to apply a temperature correction factor would I also apply it to the ampacity rating in the 90 degree column?

    Marie  December 31 2014, 2:12 pm EST
    Reply to this comment

  • you make so clear you should of written the code book

    tony   December 22 2014, 9:34 am EST
    Reply to this comment

  • Kudos to Mike Holts and his staff. Making the electrical industry more interesting.

    Jose Guzman  December 22 2014, 8:33 am EST
    Reply to this comment

  • Sizing conductors IS confusing....if feeders should be sized based on OCPD per 215.3, branch circuits should also be sized based on OCPD per 210.20(B)!?!

    I think branch circuit AND feeder conductors should be sized based on load (including adjustments using 60/75C typ lug ratings). The conductors selected should then be verified to be protected by their OCPD (including adjustments using the conductor actual rating of 60/75/90C).

    I have typically found the information excellent, but this two part series seems to have missed the mark.

    Scott  December 15 2014, 8:46 am EST
    Reply to this comment

  • Just out of curiosity, for years we have had 90 Deg C ratings for conductors that have not been available to engineers, simply because the vast majority of equipment terminals continue to be listed at 75C. Will there ever be progress by manufacturers on this issue?

    Phillip Pulliam  December 14 2014, 6:07 am EST
    Reply to this comment

  • I guess I missed Part 1. Is it still available?

    Oh, and by the way, I cannot thank Mike Holt and his staff for the premier service they perform insuring that the latest electrical safety information is available to all of us in the business. Many consultants can publish a book. Mike is the only one I know of that explains of the source material through a variety of information and communication methods including print, webinars, formal classroom, and this famous comment page.

    Bruce  December 13 2014, 5:05 pm EST
    Reply to this comment

  • Thank you for your tips. They Help.

    John Howell  December 13 2014, 9:54 am EST
    Reply to this comment

  • We have to ask ourselves Where would we be without Mike Holt and his team? I have gained so much respect in the industry because of the knowledge I have gained from Mike and his team. Ingredients Passion+drive+listening + Mike Holt & Team + local code classes with like minded people = Success.

    Bruce Angeloszek  December 12 2014, 7:59 pm EST
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter