This article was posted 12/04/2006 and is most likely outdated.

Article 810 Radio and Television Equipment
 

 
Topic - NEC
Subject
- Article 810 Radio and Television Equipment

December 4, 2006  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 810 Radio and Television Equipment

By Mike Holt for EC&M Magazine

Don’t get mixed signals when installing radio and TV antenna systems.
Article 810 provides installation requirements for transmitter and receiver equipment and the associated wiring and cabling (Figure 810-1). Article 810 applies to:

  • VHF/UHF antennas (which receive local television signals).
  • Satellite antennas (also called satellite dishes).
  • Roof-mounted antennas for AM/FM/XM radio reception.
  • Amateur radio transmitting and receiving equipment, including HAM radio equipment (a noncommercial communications system).

Requirements for all antenna systems
The first three kinds of installations in the bulleted list above involve receiving signals. The fourth one also involves transmitting, which is why amateur radio installations have additional requirements over those for receiving antenna systems installations (we’ll address those, last).

Although 90.3 states that nothing in Chapter in 8 is required to comply with chapters 1-7, section 810.3 requires that we follow Chapters 1-4 for the wiring from the power source to Article 810 equipment. Note that wiring for audio equipment must comply with Article 640.

Install coaxial cables per Article 820 [810.3], if they connect antennas to equipment. Coax cable beyond the point of entry falls under Article 820 [810.4] (Figure 810-2). You will find the grounding requirements for antenna cables in 810.20(C) and 810.21.

Outdoor antennas and lead-in conductors must be securely supported, and the lead-in conductors must be securely attached to the antenna [810.12]. Don’t attach outdoor antennas to the electric service mast [810.12 and 230.28]. Keep outdoor antennas and lead-in conductors at least 2 ft from exposed electric power conductors, to avoid the possibility of accidental contact [810.13].

Ground outdoor masts (and metal structures that support antennas) in accordance with 810.21 [810.15]. If an antenna mast is within 5 ft of a swimming pool, bond it to the equipotential bonding grid of the pool [680.26(B)(5)].

Antenna Discharge Unit
Provide a listed antenna discharge unit for each lead-in conductor of an outdoor antenna [810.20(A)]. Locate discharge units as close to the point of entrance either outside of the building, or inside the building as close to the outside as possible. Either way, make sure it is not near combustible material [810.20(B)].

Nothing can prevent damage from a direct lightning strike. But grounding with proper surge protection can help reduce damage from nearby lightning strikes. Grounding helps prevent voltage surges (caused by static discharge or nearby lightning strikes) from reaching the center conductor of the lead-in coaxial cable.

Because the antenna is outdoors, wind creates a static charge on the antenna and on the cable attached to it. This charge can build up on both the antenna and cable until it jumps across an air space, often passing through the electronics inside the “low noise block down converter feed” (LBNF) horn or receiver. Grounding helps to dissipate this static charge.

Ground the antenna mast [810.15] and antenna discharge units [810.20(C)] as specified in 810.21(A) through 810.21 (K) (Figure 810-8).

(A) Material. The grounding conductor to the electrode must be copper or other corrosion-resistant conductive material. It can be stranded or solid.
(B) Insulation. The grounding conductor can be insulated or bare.
(C) Supports. The grounding conductor must be securely fastened in place.
(D) Protection Against Physical Damage. The grounding conductor must be guarded from physical damage. If the grounding conductor is in a metal raceway, bond each end of the raceway to the grounding conductor. Installing the grounding conductor in a nonmetallic raceway, when the authority having jurisdiction judges that physical protection is required, is a better practice than using a metal raceway.
(E) Run in Straight Line. The grounding conductor must be run in as straight a line as practicable. Lightning doesn’t like to travel around corners or through loops—it tends to jump across them or from them to nearby objects.
(F) Electrode. The grounding conductor must terminate to the nearest accessible:

  • Structure grounding electrode system [250.50].
  • Interior metal water piping system, within 5 ft from its point of entrance as described in [250.52(A)(1)].
  • Service bonding means [250.94].
  • Metallic service raceway.
  • Service equipment enclosure.
  • Grounding electrode conductor or the grounding electrode conductor metal enclosure.

(G) Inside or Outside Building. The grounding conductor can be run either inside or outside the building.
(H) Size. The grounding conductor must not be smaller than 10 AWG copper or 17 AWG copper-clad steel or bronze. Copper-clad steel or bronze wire (17 AWG) is often molded into the jacket of the coaxial cable to simplify the grounding of the satellite dish by eliminating the need to run a separate ground wire to the dish.
(J) Bonding of Electrodes. If a ground rod is installed to serve as the ground for the radio and television equipment, you must connect it to the power grounding electrode system with a minimum 6 AWG conductor. The bonding of separate system electrodes reduces voltage differences that may develop between them (Figure 810-12).
(K) Electrode Connection. Termination of the grounding conductor must be by exothermic welding, listed lug, listed pressure connector, or listed clamp. Grounding fittings that are concrete-encased or buried in the earth must be listed for direct burial and marked “DB” [250.70].

Receiving equipment
If lead-in conductors are attached to buildings, install them in a way that prevents them from swinging closer than 2 ft to the conductors of circuits of 250V (or less) or closer than 10 ft to the conductors of circuits of over 250V. Keep all lead-in conductors at least 6 ft from lightning protection conductors [810.18(A)].
Also:

  • Underground antenna lead-in conductors must maintain a separation not less than 12 in. from power conductors [810.18(A)] although there is no minimum burial depth for lead-in conductors.
  • Indoor antenna and lead-in conductors must not be less than 2 in. from light and power conductors [810.18(B)].

For the two preceding requirements, you don’t need separation if you have installed the lead-in conductors or the power conductors in a raceway or cable armor. Indoor antenna lead-in conductors can be in the same enclosure with power conductors where separated by an effective, permanently installed barrier.

How big must the antenna conductor be? That depends on how long the conductor is and what it’s made of. If the conductor is [Table 810.16(A)]:

  • Less than 35 ft long, use 19 AWG copper or aluminum alloy or use 20 AWG copper-clad steel, bronze, or other high-strength material.
  • More than 35 ft long but less than 150 feet long, use 14 AWG copper (or 14 AWG aluminum alloy) or use 17 AWG copper-clad steel, bronze, or other high-strength material.
  • Longer than 150 ft, use 12 AWG copper (or 14 AWG aluminum alloy) or use 14 AWG copper-clad steel, bronze, or other high-strength material.

Transmitting (amateur radio)
Amateur radio has additional requirements beyond those for receiving equipment, because of an additional function: transmitting. Thus, if the installation is an amateur radio system, it must comply with Article 810, Part III (810.51 through 810.58).

Obviously, the antenna conductors must be larger if you are also transmitting. If the conductors are longer than 150 feet, use either 10 AWG hard-drawn copper or 12 AWG copper-clad steel, bronze, or other high-strength material. If the length is under 150 feet, you can use 14 AWG in any of the aforementioned materials [Table 810.52].

With receiving installations, you can mount the antenna lead-in conductors on the surface of the building. But with amateur radio, the antenna lead-in conductors must be firmly mounted at least 3 in. away from the surface of the building [810.54]. If the lead-in conductors are enclosed in a continuous metallic shield (coaxial), you can secure them directly to the building structure [810.54 Ex].

As with receiving systems, each lead-in conductor from an amateur radio outdoor antenna must be provided with a listed antenna discharge unit (or other suitable means that drain static charges from the antenna system) [810.57], except where:

  • Protected by a continuous metallic shield that is permanently and effectively grounded.
  • The antenna is permanently and effectively grounded.

Ground the antenna mast [810.15] and antenna discharge unit [810.57] as specified in 810.21(A) through (K), just as with the receiving stations. However, the operating grounding conductor for amateur radio installations must not be smaller than 14 AWG copper or equivalent [810.58(C)].

The sidebar provides the key points to remember about Article 810. In general, what you are trying to do is keep the antennas from picking up anything other than radio or television signals. That means providing some space from other conductors to prevent induced voltage, bonding the mast and other metallic objects to prevent differences in potential, and properly grounding to protect against lightning-induced surges.

Article 810 Key Points

  • Prevent contact with conductors of other systems.
  • Don’t attach antennas or other equipment to the service-entrance power mast.
  • If the mast isn’t grounded properly, voltage surges caused by nearby lightning strikes can destroy it. Keep the grounding conductor straight, and protect it from physical damage.
  • If the mast isn’t bonded properly, you risk flashovers and possible electrocution. Because bonding prevents a difference of potential between metallic objects and other conductive items, Article 810 provides several different bonding requirements.
  • Because clearances are critical, Article 810 provides extensive clearance requirements.

 

[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Contact our Webmaster

Comments
  • Well, he's talking about the antenna conductors (for an HF wire antenna), not the antenna "lead-in" conductors. So, for a dipole antenna that's used for 160m operation, 12- or 14-AWG copperclad steel is recommended for the dipole elements since they're on the order of 66' each.

    RG-6 and RG-59 are 75 ohm CATV-type cable. Amateur radios typically use either 50 ohm coax (like RG-8 or -58) or 600 ohm ladder line. They're heavy duty, and the center conductor of say Belden 9913 cable is about 9.5AWG...

    Jon Gauthier
    Reply to this comment

  • This is what happens when you have power people writing specs for the RF world. Does anybody really think that you're going to find RG6 or RG59 with 14AWG or 12AWG conductors, and would you want to use it?

    Rudy Rossetto
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter