Article 250 Grounding and Bonding 250.30
 

 
Subject - Article 250 Grounding and Bonding 250.30

January 19, 2007  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 250   Hi Res - Cable/DSL [7400Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
   
Grounding and Bonding

250.30 Grounding and Bonding of Separately Derived AC Systems

Text clarifies the method of sizing equipment bonding jumpers when the separately derived system conductors are run in parallel. And the text relating to the “common” grounding electrode conductor for multiple separately derived systems was changed to require this conductor not to be sized smaller than 3/0 AWG.
(A) Grounded Systems. Separately derived systems must be bonded and grounded in accordance with (1) through (8).

(2) Equipment Bonding Jumper Size. Where an equipment bonding jumper is run to the first disconnecting means, it must be sized based on the largest ungrounded secondary conductor, in accordance with Table 250.66.

Question: What size equipment bonding jumper is required for a nonmetallic raceway containing 500 kcmil conductors from the source of a separately derived system? Figure 250-10
(a) 1 AWG    (b) 1/0 AWG    (c) 2/0 AWG    (d) 3/0 AWG

Answer: (b) 1/0 AWG, Table 250.66

Where separately derived system conductors are run in parallel, the bonding jumper for each raceway or cable must be sized based on the largest ungrounded secondary conductor in each raceway or cable [250.102(C)].

(4) Grounding Electrode Conductor, Multiple Separately Derived Systems. Where there are multiple separately derived systems, it’s permissible to connect a tap from the grounded neutral terminals of each separately derived system to a common grounding electrode conductor. Each tap must connect the grounded neutral terminal of a separately derived system to the common grounding electrode conductor. The grounding electrode conductor and grounding electrode taps must comply with (a) through (c). Figure 250-11

Ex 1: Where the system bonding jumper specified in 250.30(A)(1) is a wire or busbar, the grounding electrode conductor is permitted to terminate to the equipment grounding terminal bar or bus of the separately derived system.

Ex 2: A grounding electrode conductor isn’t required for systems rated 1 kVA or less, however the system bonding jumper (neutral-to-case) connection must be installed in accordance with 250.30(A)(1).
(a) Common Grounding Electrode Conductor Size. The common grounding electrode conductor must not be smaller than 3/0 AWG copper or 250 kcmil aluminum.
(b) Tap Conductor Size. Each grounding electrode tap conductor must be sized in accordance with 250.66, based on the largest separately derived ungrounded conductor of the separately derived system.
(c) Connections. All grounding electrode tap connections must be made at an accessible location by:
(1) Listed connector
(2) Listed connections to aluminum or copper busbars not less than 1/4 × 2 in. Where aluminum busbars are used, the installation must comply with 250.64(A).
(3) By the exothermic welding process.

Grounding electrode tap conductors must be connected to the common grounding electrode conductor in a manner that the common grounding electrode conductor isn’t spliced.


Figure 250-10
(Click on image to enlarge)


Figure 250-11
(Click on image to enlarge)

     
 

[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Contact our Webmaster

Comments
  • Mike, Viewing your illustration I noticed that the primary does not have and equipment grounding conductor. In the event of a fault is the primary OCPD going to function properly.

    Ben McMillon
    Reply to this comment

  • i have a portable generator with a bonded neutral, how do i switch it over to a floating neutral

    stan
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter