This article was posted 07/07/2008 and is most likely outdated.

Motor Calculations
 

 

Topic - NEC
Subject - Motor Calculations

July 7, 2008
This newsletter was sent to 28809 newsletter subscribers

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Motor Calculations

 

By Mike Holt for EC&M Magazine

 

Motor protection and motor circuit protection require different calculations.

 

To prevent a motor from burning up, you must provide a means of protecting it from overcurrent (overload, short circuit, or ground fault). If you can remember not to confuse motor protection with circuit protection, you’ll eliminate a major point of confusion in motor calculations.

 

Looking at Figure 430.1 will help you keep this distinction clear. Notice that it shows the requirements for motor overload protection in Part III and the requirements for short-circuit and ground-fault protection in Parts IV and V.

 

Table or nameplate?

 

To determine the minimum ampacity of the motor supply conductors, you obviously need to know how much current the motor draws. But there are different types of current in motor applications (see Sidebar). Which do you use for your calculations?

 

You can’t use FLA to determine the conductor ampacity, the branch-circuit short-circuit and ground-fault overcurrent device size, or the ampere rating of disconnecting switches. Use FLA for separate motor overload protection FLA [430.6(2)]. For everything else, use the FLC tables (430.247, 430.248, and 430.250). Exceptions apply:

 

  • If you’re calculating separate motor overload protection for torque motors, use the locked rotor current value on the nameplate.
  • If a VFD controls the motor, use the maximum operating current that’s marked on the nameplate (motor or control). If that value isn’t on the nameplate, use the NEC current tables.
  • High-torque motors and those built to operate under 1,200 RPM may have higher FLCs, and the FLC of a multispeed motor varies with its speed. For such motors, use the nameplate current ratings.
  • For a listed motor-operated appliance, use the FLC marked on the nameplate of the appliance (rather than the horsepower rating) to determine the ampacity (or rating) of the disconnecting means, the branch-circuit conductors, the controller, and the branch-circuit short-circuit and ground-fault protection.

Overload Protection

 

Overload protection must comply with 430 Part III. Size overload protection devices based on the motor nameplate rating (this protects locked-rotor current damage to motor windings).

 

You can use a single overcurrent device, sized per 430.32 requirements, to protect a motor from overload, short circuit, and ground faults.

 

Branch-circuit conductor size

 

Branch-circuit conductors to a single motor must have an ampacity of not less than 125 percent of the FLC as listed in Tables 430.247 through 430.250 [430.6(A)(1)].

 

When selecting motor current from one of these tables, note that the last sentence above each table allows you to use the ampacity columns for a range of system voltages without any adjustment. Select the conductor size from Table 310.16 according to the terminal temperature rating (60ºC or 75ºC) of the equipment [110.14(C)].

 

THHN/THWN is a common conductor insulation type that can be used in a dry location at the THHN 90ºC ampacity, or in a wet location at the 75ºC ampacity for the THWN insulation type. Regardless of the conductor insulation type, size the conductor per 110.14(C).

 

In 110.14(C)(1)(a), we read that equipment terminals are rated 60ºC for equipment rated 100A or less (unless marked 75ºC). But most equipment terminals are now rated at 75ºC. Look for that specification, so you can use the 75ºC column if your conductors are also rated for 75ºC. You may save considerable money on your project if this is the case. If you can’t find that specification, use the rules of 110.14(C).

 

Test your knowledge by answering this question: What size branch-circuit conductors are required for a 7 ½ hp, three-phase, 230V motor?

(a) 14 AWG     (b) 12 AWG     (c) 10 AWG     (d) 8 AWG

 

Answer: (c) 10 AWG

 

Motor FLC – Table 430.248:

7 ½  hp, 230V, three-phase FLC = 22A

The conductor is sized no less than 125 percent of motor FLC:

22A x 1.25 = 27.50A, Table 310.16, 10 AWG rated 30A at 75ºC

The minimum size conductor permitted for building wiring is 14 AWG [310.5]; however, some local codes and many industrial facilities require branch-circuit conductors to be 12 AWG or larger.

 

Feeder conductor size

 

Perform feeder conductor size calculations the same way as for branch circuits, but use the different ampacity rules provided in 430.24. Conductors that supply several motors must have an ampacity of not less than:

(1) 125 percent of the highest rated motor FLC [430.17], plus

(2) The sum of the FLCs of the other motors (on the same line). Find the FLC in the NEC Tables [430.6(A)(1)].

 

The highest rated motor is the motor with the highest FLC [430.17]. Determine the “other motors in the group” value by balancing the motor FLCs on the feeder being sized, then select the line that has the highest rated motor on it.

 

Branch-circuit short-circuit and ground-fault protection

 

Each motor branch circuit must be protected against short circuit and ground faults by an overcurrent device sized no greater than the percentages listed in Table 430.52.

 

The motor branch-circuit short-circuit and ground-fault protective device must be capable of carrying the motor’s starting current, and it must comply with 430.52(b) and 430.52(C).

 

A branch-circuit short-circuit and ground-fault protective device protects the motor, the motor control apparatus, and the conductors against short circuits or ground faults, but not against overload [430.51].

 

It bothers many electrical practitioners to see a 14 AWG conductor protected by a 30A circuit breaker, but branch-circuit conductors are protected against overloads by the overload device. That device is sized between 115 and 125 percent of the motor nameplate current rating [430.32]. See 240.4(G) for details.

 

Where the branch-circuit motor short-circuit and ground-fault protective device values derived from Table 430.52 don’t correspond with the standard overcurrent device ratings listed in 240.6(A), you can use the next higher overcurrent device rating.

 

The “next size up protection” rule for branch circuits [430.52(C)(1) Ex 1] doesn’t apply to the motor feeder overcurrent device rating (Part II).

 

Keeping it straight

 

Articles 430 and 250 are the largest of the NEC Articles, and arguably the most misapplied. Something else these two Articles have in common with each other but not with the other Articles is a “Figure 1” that you can use as a guide.

 

In the case of Article 430, this figure is a simple representation of the motor system with the correct Part of Article 430 noted for each area of application. At the start of this article, we said that using Figure 430.1 will help you not confuse motor protection with circuit protection. It can do much more for you. Spend some time working with it, and you will see how useful it really is.

 

If you base each motor project on Figure 430.1, you will reduce—if not eliminate—Article 430 application errors.

 

Sidebar: Motor currents

 

Nameplate rating (FLA). The Full Load Amperes (FLA) is the current the motor draws while producing its rated horsepower load at its rated voltage.

 

NEC Tables (FLC). The Full Load Current (FLC) is the current value listed in the NEC.

 

The actual current drawn by the motor depends upon the driven load and on the operating voltage at the motor terminals. If the load increases, the current also increases. If the motor operates at a voltage below its nameplate rating, the operating current will increase.

 

It’s helpful to also understand:

  • Motor-Starting Current. When voltage is first applied to the field winding of an induction motor, only the conductor resistance opposes the flow of current through the motor winding. Because the conductor resistance is so low, the motor will have a very large inrush current.
  • Motor-Running Current. Once the rotor begins turning, there is an increase in counter-electromotive force which reduces the starting current to running current.
  • Motor Locked-Rotor Current (LRC). If the rotating part of the motor winding (armature) becomes jammed so it can’t rotate, no counter-electromotive force (CEMF) will be produced in the motor winding. This results in a decrease in conductor impedance to the point that it’s effectively a short circuit. Result—the motor operates at locked-rotor current (LRC), often six times the full-load ampere rating, depending on the motor Code Letter rating [430.7(B)]. This will cause the motor winding to overheat and be destroyed if the current isn’t quickly reduced or removed.
Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

 
Comments
  • WHERE IS FIGURE 430.1

    AZZA
    Reply to this comment

  • On a pool is the bond suppose to be continous all the way back from the motor to the source.

    Greg
    Reply to this comment

  • Thank you Mike,

    Having to deal with the term "horsepower" and the European community's concept of horsepower as a "marketing tool", rather than an accurate rating, has caused quite a few headaches on my part. It is only recently, that I have seen correct ratings, or even a code letter for that matter. I am going to forward this Newsletter to my Cohorts across the "pond".

    Mark Prairie

    Mark Prairie
    Reply to this comment

  • Mike,

    You forgot that for a motor that operates on a duty cycle, larger than 125% conductors are required. For a continuous duty rated motor under periodic or intermittent duty, the motor branch circuit conductors need to be 140% of motor full load current. For varying duty applications such some machine tools subject to force feeding, a lot of rubbish compactors, and roller coaster hoist chain motors, you need more like 200% conductors.

    The definition of varying duty in Article 100 is a bunch of nonsense, but I would define it as heavy deliberate overloading followed by a long cool down period. A lot of rubbish compactors draw 200% of full load current during part of the cycle. Similarly, it is also acceptable for a roller coaster to use that much when there are a bunch of fat people on the train.

    These values take into things like voltage drop and frequent starting and stopping for some of these loads. The ampacity requirement should also be applied to the AC-1 rating of a motor controller or circuit breaker so that you do not spot weld contacts creating something that isn't a motor controiller or circuit breaker.

    You also need to watch the rating of mechanical components. Deliberate overloads can squeeze oil out from between gear teeth and kill a gearbox.

    The gotcha that I have encountered in the industrial environment is that every once in a while the motor, motor controller, gear boxes, and so forth need to be upgraded because a 3 HP motor will not carry 3.5 HP so a 5 HP motor and controller are needed. In some cases the motor needs to be oversized enough that motor overload relays can be set at LESS THAN motor full load current.

    Michael R.Cole
    Reply to this comment

  • thank you for all the information provided

    fazah fred
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter