Pull Boxes and Junction Boxes


March 21, 2022
Share: Facebook Twitter

Figure 01

By Mike Holt
NEC® Consultant for EC&M Magazine

Note: This article is based on the 2020 NEC.

Taking the mystery out of sizing pull boxes and junction boxes.

Pull boxes, junction boxes, and conduit bodies must be sized to allow conductors 4 AWG and larger to be installed without damage to the conductor insulation. The NEC provides sizing requirements in 314.28.

Keep in mind these requirements address conductors used for general wiring, such as those identified in Table 310.16. The requirements do not apply to other types of wiring or cabling. A specialty signal cable might have a bend radius of 24 inches and that would require a significantly larger pull box than what you’d use for a general wiring conductor of a similar sized outer jacket.

Minimum dimensions
For straight pulls when raceways contain conductors 4 AWG or larger, the minimum distance from where the raceway containing conductors enter to the opposite wall must be at least eight times the trade size of the largest raceway. A straight-pull calculation applies when raceways containing conductors enter one side of a box and leave through the opposite wall of the box [314.28(A)(1)].
For other types of pulls where the raceways contain conductors 4 AWG or larger, these rules apply [314.28(A)(2)]:

  • Angle Pulls. These occur when raceways containing conductors enter a wall and leave through one that’s 90 degrees from the entry wall. The distance from the raceway entry to the opposite wall must be at least six times the trade size of the largest raceway, plus the sum of the trade sizes of the remaining raceways on the same wall and row.
  • U Pulls. A raceway containing conductors that enters and leaves from the same wall is a U pull. The distance from where the raceways enter to the opposite wall must be at least six times the trade size of the largest raceway, plus the sum of the trade sizes of the remaining raceways on the same wall and row.
  • Splices. When conductors are spliced, the distance from where the raceways enter to the opposite wall must be at least six times the trade size of the largest raceway, plus the sum of the trade sizes of the remaining raceways on the same wall and row.
  • Rows. Where there’s more than one row of raceway entries on the same wall, each row is calculated individually and the row with the largest distance must be used.
  • Distance Between Raceway Entries. The distance between raceway entries enclosing the same conductor must be at least six times the trade size of the largest raceway, measured from the raceways’ opening nearest edge to nearest edge. Figure 01

The measurement between raceway entries is taken from the actual raceway entry, not the locknuts or bushings used to terminate the raceways.
When conductors enter an enclosure with a removable cover, such as a conduit body or wireway, the distance from where the conductors enter to the removable cover must be at least the bending distance listed in Table 312.6(A) for one conductor per terminal [314.28(A)(2) Ex].

Pull box example 1
A junction box contains four trade size 3 raceways: two on the left side, one on the right side, and one on the bottom. The conductors from one of the trade size 3 raceways on the left wall are pulled through the trade size 3 raceway on the right wall. The conductors from the other trade size 3 raceway on the left wall are pulled through a trade size 3 raceway at the bottom of the pull box.

Horizontal Dimension
Question: What’s the horizontal dimension of this box?
(a) 18 in.          (b) 21 in.          (c) 24 in.          (d) 30 in.
Solution:
Left to Right Straight Pull = 8 × 3 in. = 24 in.
Right to Left Straight Pull = 8 × 3 in. = 24 in.
Left to Right Angle Pull = (6 × 3 in.) + 3 in. = 21 in.
Right to Left Angle Pull = no calculation
Answer: (c) 24 in. [314.28]

Vertical Dimension
Question: What’s the vertical dimension of a junction box having a trade size 3 raceway on the bottom wall of the junction box with no raceway on the top wall of the box?
(a) 18 in.          (b) 21 in.          (c) 24 in.          (d) 30 in.
Solution:
Top to Bottom Straight = no calculation
Bottom to Top Straight = no calculation
Top to Bottom Angle = no calculation
Bottom to Top Angle = 6 × 3 in. = 18 in.
Answer: (a) 18 in. [314.28]

Distance Between Raceway Entries
Question: What’s the minimum distance between the two trade size 3 raceways containing the same conductors?
(a) 18 in.          (b) 21 in.          (c) 24 in.          (d) 30 in.
Solution:
6 × 3 in. = 18 in.
Answer: (a) 18 in. [314.28]

Pull box example 2
A pull box contains a trade size 2 and trade size 3 raceway on the left side, a trade size 3 raceway on the top, and a trade size 2 raceway on the right side. The trade size 2 raceways are a straight pull and the trade size 3 raceways are an angle pull.

Horizontal Dimension
Question: What’s the horizontal dimension of a junction box having trade size 2 and 3 raceways on the left wall, and a trade size 2 raceway on the right wall of the box?
(a) 20 in.          (b) 24 in.          (c) 28 in.          (d) 30 in.
Solution:
Left to Right Straight Pull = 8 × 2 in. = 16 in.
Right to Left Straight Pull = 8 × 2 in. = 16 in.
Left to Right Angle Pull = (6 × 3 in.) + 2 in. = 20 in.
Right to Left Angle Pull = no calculation
Answer: (a) 20 in. [314.28(A)(2)]

Vertical Dimension
Question: What’s the vertical dimension of a junction box having a trade size 3 raceway on the top with no raceways on the bottom wall of the box?
(a) 14 in.          (b) 18 in.          (c) 21 in.          (d) 26 in.
Solution:
Top to Bottom Straight = no calculation
Bottom to Top Straight = no calculation
Top to Bottom Angle = 6 × 3 in. = 18 in.
Bottom to Top Angle = no calculation
Answer: (b) 18 in. [314.28(A)(2)]

Distance Between Raceways
Question: If the two trade size 3 raceways contain the same conductors, what’s the minimum distance between these raceways?
(a) 18 in.          (b) 21 in.          (c) 24 in.          (d) 30 in.
Solution:
6 × 3 in. = 18 in.
Answer: (a) 18 in. [314.28(A)(2)]

Always draw out problems involving junction or pull boxes, so you can visualize them and properly apply the calculations you’ve learned.

Sidebar: Tips for Pull Box Sizing

Tips for learning
Tip 1:   Pull Box calculations become easier with more practice. Use practical field examples to practice calculations.
Tip 2:   Draw up some sample pull boxes and calculate them.
Tip 3:   Obtain drawings from a completed project and “reverse engineer” the box sizes by calculating them.

Tips for doing
Tip 1:   Draw out the problem.
Tip 2:   To avoid simple mistakes, take your time and be methodical.
Tip 3:   Do one wall at a time and remember which wall you’re working on.
Tip 4:   Calculate the HORIZONTAL distance(s):

  • Left to right straight calculation
  • Right to left straight calculation
  • Left to right angle or U pull calculation
  • Right to left angle or U pull calculation

Tip 5:   Calculate the VERTICAL distance(s):

  • Top to bottom straight calculation
  • Bottom to top straight calculation
  • Top to bottom angle or U pull calculation
  • Bottom to top angle or U pull calculation

Tip 6:   Calculate the distance between raceways enclosing the same conductors.


Stay Connected:
instagram
facebook
linkedin
twitter
Comments
    No comments to display

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter