The Use of Concrete-Enclosed Reinforcing Rods as Grounding Electrodes
 

 
Topic - Grounding and Bonding
Subject - The Use of Concrete-Enclosed Reinforcing Rods as Grounding Electrodes

March 22, 2006  

| Ask a Question |  Code Graphic Code Quiz - All New! |  Free Stuff Instructors | Feedback
Online Training Products | Seminars | SubscribeUnsubscribe |
Change Email Address |
[ image1 Please Reply With Your Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

The Use of Concrete-Enclosed Reinforcing Rods as Grounding Electrodes

 

The findings of Ufer that metal encased in concrete performs as an effective grounding electrode constitutes a major breakthrough in grounding technology. This has been recognized to the extent that copper wire embedded in the concrete footings of a structure is now an acceptable alternate to driven rods or pipe electrodes in the soil. This comes as a welcome relief from the condition of ineffective grounding by the use of water pipes due to insulated material or couplings and the antagonism of the proprietors of the water pipes.

 

Click here to read this document in its entirety.

 

[ View More Newsletters ] [ Please Reply With Your Comments | View Comments | Notify Me When Comments Are Added ]

F o r w a r d   t h i s   N e w s l e t t e r   t o   a   F r i e n d !
Do you have a friend, relative, or colleague who you think would be interested in receiving this free newsletter? If so, we encourage you to forward this message along to them. If you received this email from someone else, and wish to receive your own free issues of our newsletter, sign up today!

C o n t a c t    I n f o r m a t i o n
 

Copyright © 2002, 2003, 2004, 2005 Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Comments
  • " * I have to wonder if the same effective earth ground can be obtained by encasing a #4 AWG conductor or a 20' piece of 1/2" rebar in the concrete slab of a basement. Why does the UFER ground need to be in the footing?"

    I believe the intent is to connect to the existing rebar at the point at which there is the highest occurance of moisture in the surrounding soil. I believe the pressure of the structure resting on the footer would enhance the connection of the concrete-encased electrode to the earth.

    The more rebar that is tied together, the better and more redundant the connection to earth would be. Therefore, in my opinion, the use of the rebar would be a superior connection to earth as opposed to the 20 feet of #4 method.

    "What about burying a 20' piece of rebar 12" in the dirt, then pouring concrete over it?"

    That would not be a CCE according to 250.52(A)(3), as it is to be encased by 2" of concrete. If you pour over rebar laying on the ground, then it's not encased: the underside is not in contact with the concrete.

    "Would that not provide an effective ground?" Whether it did or not, it would not be considered a true grounding electrode by the NEC, in my opinion.

    In my opinion, the rebar is to connect the Grounding Electrode Conductor to the concrete, which in turn in porous, which in turn absorbs water, which all taken together makes a killer connection to the earth.



Reply to this comment