Grounding vs Bonding: 250.119 Identification of Equipment Grounding (Bonding) Conductor

July 7, 2006  

  View Comments | Add Comments | Notify Me When Comments Are Added  

PART VI.   Hi Res - Cable/DSL [15740Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
Sections

250.119 Identification of Equipment Grounding (Bonding) Conductor.

Unless required to be insulated, equipment grounding (bonding) conductors can be bare.

Author’s Comment: Equipment grounding (bonding) conductors must be insulated for patient care equipment [517.13(B)] and permanently installed pool, outdoor spa, and outdoor hot tub equipment [680.21(A)(1), 680.23(F)(2), and 680.25(B)].
Individually covered or insulated equipment grounding (bonding) conductors must have a continuous outer finish that is either green or green with one or more yellow stripes.

Author’s Comment: Isolated ground circuits [250.96(B)] and isolated ground receptacles [250.146(D)] frequently use a green insulated conductor for equipment and a green insulated conductor with yellow stripes for the sensitive electronic equipment. Figures 250–165 and 250–166
Conductors with insulation that is green, or green with one or more yellow stripes cannot be used for an ungrounded or grounded neutral conductor. Figure 250–167

Author’s Comment: The NEC neither requires nor prohibits the use of the color green for the identification of bonding and grounding electrode conductors. Figure 250–168

(A) Conductors Larger Than 6 AWG

(1) Identified Where Accessible. Equipment grounding (bond¬ing) conductors larger than 6 AWG that are insulated can be permanently reidentified at the time of installation at every point where the conductor is accessible.

Exception: Identification of equipment grounding (bonding) conductors larger than 6 AWG in conduit bodies is not required.

(2) Identification Method. Equipment grounding (bonding) conductor identification must encircle the conductor and be accomplished by one of the following:
(a) Stripping exposed insulation
(b) Coloring exposed insulation green
(c) Marking exposed insulation with green tape or green adhesive labels

 

imageSend to a Friend


Figure 250–165
(Click on image to enlarge)


Figure 250–166
(Click on image to enlarge)


Figure 250–167
(Click on image to enlarge)


Figure 250–168
(Click on image to enlarge)

 

Copyright © 2006 Mike Holt Enterprises,Inc.
1-888-NEC-CODE (1-888-632-2633)

 

Comments
  • What is a problem right now is that a 500 foot reel of #10 THWN wire is around $115 locally. On small jobs when running a 30 amp branch circuit in conduit and having to buy 3 reels ( black, white, and green ) is a very real financial hardship.

    Most of the supply houses are willing to cut #8 and #6 THWN but not #10 THWN. For what the big boxes charge for cut to length #10 THWN I could just as easily get #8 from a supply house cut to length particularly if the supply house is closer.

    It used to be that licensed electricians could just run black #10 THWN or any other hot color and then tag the neutral and equipment ground with white and green tape respectively. NFPA does not seem to get it that many customers are not made out of money and that I have to ring out and color 2 or 3 hot wires anyways. Ringing aout and tagging neutral and equipment ground is not that much harder!

    Mike Cole, mc5w at earthlink dot net

    Michael R. Cole

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter