Article 250 Grounding and Bonding 250.34
 

 
Subject - Article 250 Grounding and Bonding 250.34

January 26, 2007  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 250   Hi Res - Cable/DSL [6312Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
  
Grounding and Bonding

250.34 Generators – Portable and Vehicle-Mounted

Revision clarifies when portable and vehicle-mounted generators are not required to be grounded to a grounding electrode.

(A) Portable Generators. The frame of a portable generator isn’t required to be grounded to a grounding electrode as defined in 250.52 if: Figure 250-13
(1) The generator only supplies equipment or receptacles mounted on the generator, and (2) The metal parts of the generator and the receptacle terminal for the connection of the equipment grounding (bonding) conductor are bonded to the generator frame.


(B) Vehicle-Mounted Generators. The frame of a vehicle-mounted generator isn’t required to be grounded to a grounding electrode as defined in 250.52 if: Figure 250-14
(1) The generator frame is bonded to the vehicle frame,
(2) The generator only supplies equipment or receptacles mounted on the vehicle or generator, and
(3) The metal parts of the generator and the receptacle terminal for the connection of the equipment grounding (bonding) conductor are bonded to the generator frame.



Figure 250-13
(Click on image to enlarge)


Figure 250-14
(Click on image to enlarge)

     
 

[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Contact our Webmaster

Comments
  • "For proper operation of a two pole GFCI breaker supplying a two wire 240v receptacle (L6-20R), a solid neutral/equipment ground bond is required on a vehicle mounted generator system".

    True or False?

    (I know this has nothing to do with a grounding electrode, just curious.)

    Mark Prairie

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter