Article 314 Outlet Device, Pull and Junction Boxes, Conduit Bodies, and Handhole Enclosures
 

 
Subject - Article 314 Outlet Device, Pull and Junction Boxes, Conduit Bodies, and Handhole Enclosures

March 2, 2007  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 314   Hi Res - Cable/DSL [5112Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
Outlet, Device, Pull and Junction Boxes, Conduit Bodies, and Handhole Enclosures

314.30 Handhole Enclosures

New section contains the requirements for handhole enclosures.
Handhole enclosures must be designed and installed to withstand all loads likely to be imposed.

FPN: See ANSI/SCTE 77, Specification for Underground Enclosure Integrity, for additional information on deliberate and nondeliberate traffic loading that can be expected to bear on underground enclosures.

(A) Size. Handhole enclosures must be sized in accordance with 314.28(A). For handhole enclosures without bottoms, the measurement to the removable cover is taken from the end of the conduit or cable assembly.

(B) Mechanical Connection. Underground raceways and cable entering a handhole enclosure aren’t required to be mechanically connected to the handhole enclosure
. Figure 314-8

(C) Handhole Enclosures Without Bottoms. All splices or terminations must be listed as suitable for wet locations.

(D) Covers. Handhole enclosure covers must have an identifying mark or logo that prominently identifies the function of the enclosure, such as “electric.”

Handhole enclosure covers must require the use of tools to open, or they must weigh over 100 lb. Metal covers and other exposed conductive surfaces must be bonded
to an effective ground- fault current path in accordance 250.96(A) [250.4(A)(3)].


Figure 314-8
(Click on image to enlarge)

       
 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

Comments
  • The big problem with handholes is the entrapment of water, it some areas drainage is not adaquate. Over time most connections will fail, there is a differenc between being suitable for wet locations and being underwater.

    Bill Sims

Reply to this comment
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

This newsletter is closed to new comments.

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter