Article 330 Metal-Clad Cable: Type MC - 330.108
 

 

Subject - Article 330 Metal-Clad Cable: Type MC - 330.108

March 30, 2007  

Ask a Question |  Weekly Code GraphicQuizzes |  Free Stuff InstructorsOnline Training Products | Seminars | SubscribeUnsubscribe
[ image1 Post Comments | View Comments | Notify Me When Comments Are Added ] Web Page Version [Printer-Friendly]    

Article 330   Hi Res - Cable/DSL [3630Kb]
VIEWING Video FILE requires
Real Media Player [ FREE ]
Metal-Clad Cable: Type MC

330.108 Equipment Grounding (Bonding)

Section rewritten to clarify when Type MC cable is permitted to serve as an equipment grounding (bonding) path.
Where MC cable is used for equipment grounding it must comply with 250.118(10) and 250.122.

Author’s Comment: The armor on interlocked Type MC cable isn’t listed as an equipment grounding (bonding) conductor (effective ground-fault current path), therefore an equipment grounding (bonding) conductor must be installed within the metal armor wrap [250.118(10)]. Figure 330-4


Figure 330-4
(Click on image to enlarge)

       
 

Click here to post a comment
[ View More Newsletters ] [ Send to a Friend ] [ Post Comments | View Comments | Notify Me When Comments Are Added ]

Copyright © Mike Holt Enterprises, Inc. All rights reserved.
This article is protected by United States copyright and other intellectual property laws and may not be
displayed or published on the internet without the prior written permission of Mike Holt Enterprises, Inc.

http://www.MikeHolt.com     1-888-NEC-CODE (1-888-632-2633)

Experiencing a Problem? Click Here

Comments
  • Can this equipment grounding conductor be bare inside the MC cable or does it have to be insulated? Thanks Joe

    Joe Wells
    Reply to this comment

  • We are trying a "new" type of MC cable called mc-ap. It has a bare #10 aluminum ground wire, which is in intimate contact with the armor. At termination, we simply strip back the armor, bend the ground wire back over and cut it flush with the end of the armor. When used with proper connectors, it is listed as a grounding means. This saves us from spicing the ground wires and pigtailing them to the box. Saves room in the boxes also.

    Joe V
    Reply to this comment

  • I think manufactures have had their hands in this for a long time now. MC,armored cable,bx,basically all the same. When are they going to have just one type of cable with the same rule for all? If they are able to get bx approved for grounding they could get MC as well if they had the will.Mike, any thoughts?

    john villafane
    Reply to this comment


Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter