Mike Holt Enterprises Electrical News Source

NEC Questions and Answers based on 2017 NEC - January 2019

View in browser

Figure 01

For EC&M Magazine
By Mike Holt, NEC® Consultant

Here's the follow-up to yesterday's newsletter.
This includes the answers to the questions sent, so you can see how you did.

Note: The answers to these questions are based on the 2017 NEC. Underlined text indicates a change in the rule for the 2017 NEC.

Q1. Which alternating-current systems are required to be grounded by the NEC?
A1. Systems operating below 50V aren’t required to be grounded or bonded in accordance with 250.30 unless the transformer’s primary supply is from [250.20(A)]:
(1) A 277V or 480V system.
(2) An ungrounded system.
The following 50V to 1,000V systems must be grounded (connected to the earth) [250.20(B)]:
(1) Single-phase systems where the neutral conductor is used as a circuit conductor.
(2) Three-phase, wye-connected systems where the neutral conductor is used as a circuit conductor.
(3) Three-phase, high-leg delta-connected systems where the neutral conductor is used as a circuit conductor.

Q2. What are the Code permitted methods for the termination of the grounding electrode conductor for a grounded system?
A2. Service equipment supplied from a grounded system must have the grounding electrode conductor terminate in accordance with 250.24(A).
Grounding Location. A grounding electrode conductor must connect the service neutral conductor to the grounding electrode at any accessible location, from the load end of the overhead service conductors, service drop, underground service conductors, or service lateral, up to and including the service disconnect [250.24(A)(1)].

Author’s Comment:
• Some inspectors require the service neutral conductor to be grounded (connected to the earth) from the meter socket enclosure, while other inspectors insist that it be grounded (connected to the earth) only from the service disconnect. Grounding at either location complies with this rule.

Grounding Termination. When the service neutral conductor is connected to the service disconnect [250.24(B)] by a wire or busbar [250.28], the grounding electrode conductor can terminate to either the neutral terminal or the equipment grounding terminal within the service disconnect [250.24(C)(4)].

Neutral to Case Connection. A neutral to case connection isn’t permitted on the load side of service equipment, except as permitted by 250.142(B) [250.24(A)(5)].

Author’s Comment:
• If a neutral to case connection is made on the load side of service equipment, dangerous objectionable neutral current will flow on conductive metal parts of electrical equipment [250.6(A)]. Objectionable neutral current on metal parts of electrical equipment can cause electric shock and even death from ventricular fibrillation, as well as a fire.

Q3. Where does the Code require that the connection be made between the neutral conductor and the equipment grounding conductor at a service?
A3. A main bonding jumper [250.28] is required to connect the neutral conductor to the equipment grounding conductor within the service disconnect [250.24(B)].

DANGER: If the Main Bonding Jumper Is Not Installed: Dangerous voltage from a ground fault will not be removed from metal parts, metal piping, and structural steel if the service disconnect enclosure is not connected to the service neutral conductor. This is because the contact resistance of a grounding electrode to the earth is so great that insufficient fault current returns to the power supply if the earth is the only fault current return path available to open the circuit overcurrent protection device. Figure 01

Q4. The neutral of a grounded utility service must be installed and terminated at what location in accordance with the NEC?
A4. A service neutral conductor must be run from the electric utility power supply with the ungrounded conductors and terminate to the service disconnect neutral terminal [250.24(C)]. A main bonding jumper [250.24(B)] must be installed between the service neutral terminal and the service disconnect enclosure [250.28].

Author’s Comment:
• The service neutral conductor provides the effective ground
fault current path to the power supply to ensure that dangerous voltage from a ground fault will be quickly removed by opening the overcurrent protection device [250.4(A)(3) and 250.4(A)(5)].
• Even if the service equipment is only supplying loads with no neutral conductor, such as a three-phase motor, a service neutral conductor between the utility and service is part of the effective ground fault current path needed in case there is a ground fault condition.

DANGER: Dangerous voltage from a ground fault won’t be removed from metal parts, metal piping, and structural steel if the service disconnect enclosure isn’t connected to the service neutral conductor. This is because the contact resistance of a grounding electrode to the earth is so great that insufficient fault current returns to the power supply if the earth is the only fault current return path to open the circuit overcurrent protection device.

Author’s Comment:
• If the neutral conductor is opened, dangerous voltage will be present on metal parts under normal conditions, providing the potential for electric shock. If the earth’s ground resistance is 25 ohms and the load’s resistance is 25 ohms, the voltage drop across each of these resistors will be half of the voltage source. Since the neutral is connected to the service disconnect, all metal parts will be elevated to 60V above the earth’s voltage for a 120/240V system.

Q5. What does the Code require as a minimum size for the service neutral conductor?
A5. Neutral Sizing for Single Raceway or Cable [250.24(C)(1)]. Because the service neutral conductor serves as the effective ground fault current path to the source for ground faults, the neutral conductor must be sized so it can safely carry the maximum fault current likely to be imposed on it [110.10 and 250.4(A)(5)]. This is accomplished by sizing the neutral conductor not smaller than specified in Table 250.102(C)(1), based on the cross sectional area of the largest ungrounded service conductor.

Author’s Comment:
• In addition, the neutral conductors must have the capacity to carry the maximum unbalanced neutral current in accordance with 220.61.

Example: What’s the minimum size service neutral conductor required where the ungrounded service conductors are 350 kcmil and the maximum unbalanced load is 100A?
Answer: 2 AWG is the minimum size service neutral conductor required [Table 250.102(C)(1)].
The unbalanced load of 100A requires a 3 AWG service neutral conductor, which is rated 100A at 75ºC in accordance with Table 310.15(B)(16) [220.61], but the neutral conductor can’t be smaller than 2 AWG to carry fault current, based on the 350 kcmil ungrounded conductors in accordance with Table 250.102(C)(1).

Neutral Sizing for Parallel Conductors in Two or More Raceways or Cables [250.24(C)(2)]. If service conductors are paralleled in two or more raceways or cables, a neutral conductor must be installed in each of the parallel raceways or cables. The size of the neutral conductor in each raceway or cable isn’t permitted to be smaller than specified in Table 250.102(C)(1), based on the cross sectional area of the largest ungrounded service conductor in each raceway or cable. In no case can the neutral conductor in each parallel set be sized smaller than 1/0 AWG [310.10(H)(1)].

Author’s Comment:
• In addition, the neutral conductors must have the capacity to carry the maximum unbalanced neutral current in accordance with 220.61.

Example: What’s the minimum size service neutral conductor required for each of two raceways, where the ungrounded service conductors in each of the raceways are 350 kcmil and the maximum unbalanced load is 100A?
Answer: The minimum size service neutral conductor required is 1/0 AWG per raceway [Table 250.102(C)(1) and 310.10(H)].
The unbalanced load of 50A in each raceway requires an 8 AWG service neutral conductor, which is rated 50A at 75ºC in accordance with Table 310.15(B)(16) [220.61]. Also, Table 250.102(C)(1)
requires a minimum of 2 AWG in each raceway, however, 1/0 AWG is the smallest conductor permitted to be paralleled [310.10(H) and Table 310.15(B)(16)].

Comments
    No comments to display

Get notified when new comments are posted here
* Your Email:
 
        
 
Add Your Comments to this Newsletter
* Your Name:
   Your name will appear under your comments.

* Your Email:
   Your email address is not displayed.
* Comments:

Email Notification Options:
Notify me when a reply is posted to this comment
Notify me whenever a comment is posted to this newsletter