Illustrated Changes to the NEC, 2005 Edition - Part 2

Article 400

Flexible Cords

400.14 Protection from Damage

New paragraph permits flexible cords to be installed in above ground raceways in industrial environments in lengths up to 50 ft, but only under restricted conditions.

Flexible cords must be protected by bushings or fittings where passing through holes in covers, outlet boxes, or similar enclosures.

In industrial establishments where the conditions of maintenance and supervision ensure that only qualified persons will service the installation, flexible cords not exceeding 50 ft can be installed in above ground raceways.