| Part TWO
Electrical equipment is designed to operate at within a given voltage range, typically
no less than 10% and no more than 5% from its voltage rating.
Example: A typical 230 volt load is designed to operate at not less than 207 volts (-10%)
and not more than 242 volts (+5%), Figure 1.
Authors Comment: Figures are not posted on the internet.
The actual operating voltage dependents on the output voltage from the electric utility
and the voltage drop of the circuit conductors. Keep in mind that the voltage from the
electric utility is not constant; its lower during peak utility loading and higher during
off-peak load periods.
Generally, overvoltage in an electrical system is not a problem, unless there is a wiring
error in the electrical system1, however reduced or under voltage can caused inconvenience
by flickering lights2, erratic performance of electro-mechanical devices such as relays
and contactors, fires, and equipment failures. In particular, sensitive electronic equipment
operating at reduced voltage will not have sufficient ride-through capability
for voltage sags, and fire pump equipment possibly could fail at inadequate voltage.
1See http://www.mikeholt.com/Newsletters/campus.htm for case studies on overvoltage.
2 See http://www.mikeholt.com/Newsletters/10-7-99.htm for case studies on flickering
lights.
Electric utilities are required by public service commissions to supply electrical power
with sufficient voltage and capacity for the loads to be served and for most installations,
this is not a problem. Reduced or under voltage is often caused by excessive long service,
feeder, and or branch circuit conductors. The sizing of these conductors is important
to insure proper operating voltage for a safe and efficient electrical systems.
The actual equipment operating voltage is dependent on the originating voltage, the conductor
size (actually its resistance), and the magnitude of the current flowing through the circuit
conductors. The originating voltage at times can be increased by adjusting the taps on
the transformer and the circuit voltage drop can be reduced by decreasing the load or
increasing the conductor circular mil area.
Last month I explained that the Fine Print Notes (FPN) in the NEC about voltage drop is
not enforceable as a Code rule. However, The National Electrical Code does require conductors
to be sized to accommodate voltage drop for the following purposes:
· Grounding Conductors Section
250-122(b)
· Motion Picture/Television Studios
Section 530-71(d)
· Fire Pumps Section 695-7
The following formulas can be used to properly size conductors to prevent excessive voltage
drop:
CM (single-phase) = (2 x K x I x D)/VD
CM (three-phase) = (1.732 x K x I x D)/VD
Author's Comment: Download a free Windows 95 Voltage Drop Calculator from www.mikeholt.com.
CM = Circular-Mils: The circular mils of the circuit conductor as listed in
Chapter 9, Table 8.
K = Direct Current Constant: The direct current constant value to be used for
copper is 12.9 ohms and 21.2 ohms is used for aluminum conductors.
Q = Alternating Current Adjustment: Alternating current circuits No. 2/0 and
larger must be adjusted for the effects of self-induction (skin effect). The "Q"
adjustment factor is determined by dividing alternating current resistance as listed in
NEC Chapter 9, Table 9, by the direct current resistance as listed in Chapter 9, Table
8.
I = Amperes: The load in amperes at 100 percent, not 125 percent for motors
or continuous loads.
D = Distance: The distance the load is located from the power supply, not the
total length of the circuit conductors.
VD = Volts Dropped: The voltage drop of the circuit conductors as expressed
in volts.
Example Single-Phase
A 5 horsepower motor is located 100 feet from a 120/240 volt panelboard. What size conductor
should be used if the motor nameplate indicates the voltage range is between 208-230 volts.
Limit the voltage drop to 7.2 volts (3% of the voltage source) and the terminals are rated
75ºC, Figure 2.
(a) No. 10 THHN (b) No. 8 THHN
(c) No. 6 THHN (d) No. 4 THHN
Answer: (a) No. 10 THHN
Section 430-22(a) requires motor conductors to be sized not less than 125 percent of the
motor full-load current (28 amperes) as listed in Table 430-148. A No. 10 is rated 35
amperes at 75ºC [Table 310-16 and Section 110-14(c)] and it is suitable to meet the
NEC requirements (28 ampere x 1.25 = 35 ampere). In addition, a No. 10 conductor limits
the voltage drop to meet the manufactures voltage limitation rating [110-3(b)].
Conductor required to limit voltage drop to 3%
CM = (2 x K x I x D)/VD
CM = Wire size, Chapter 9, Table 8
K = 12.9 ohm, copper
I = 28 ampere
D = 100 feet
VD = 240 volts x 3% = 7.2 volts
CM = (2 x 12.9 ohms x 28 amperes x 100 feet)/7.2 volts
CM = 10,033, No. 10, Chapter 9, Table 8
Example Three-Phase
Example: A 25 horsepower, 208 volt three-phase fire pump motor is located 175 feet the
service. The fire pump motor controller is located 150 feet from the service (motor 25
feet from controller). What size conductor must be installed to the fire pump motor? Note:
Terminals are rated 75ºC, Figure 3.
(a) No. 4 THHN (b) No. 3 THHN
(c) No. 2 THHN (d) No. 1 THHN
Answer: (b) No. 3 THHN
When sizing conductors for fire pump motors the following rules must be considered.
Calculation 1.
Section 695-6(c)(2) No. 3. Branch circuit conductors must be sized no less than
125 percent of the fire pump motor full-load current as listed in Table 430-148 or 430-150,
based on 75°C terminal rating [110-14(c)(1)] as listed in Table 310-16.
74.8 ampere x 1.25 = 93.4 ampere, No. 3 THHN at 75°C is rated 100 ampere
Calculation 2.
Section 695-7 No. 3. The operating voltage at the motor controller terminals shall
not drop more than 15 percent below the controller-rated voltage when the motor starts
(lock-rotor current).
CM = (1.732 x K x I x D)/VD
CM = Wire size, Chapter 9, Table 8
K = 12.9 ohms, copper
I = 404 ampere (locked-rotor, Table 430-151B)
D = 150 feet
VD = 31.2 volts (208 volts x 15%)
CM = (1.732 x 12.9 ohms x 404 ampere x 150 feet)/31.2 volts
CM = 43,396, Chapter 9, Table 8 = No. 3
Calculation 3.
Section 695-7 No. 4. The operating voltage at the terminals of the motor shall not
drop more than 5 percent below the voltage rating of the motor while the motor is operating
at 115 percent of the full-load current rating of the motor.
CM = (1.732 x K x I x D)/VD
CM = Wire size, Chapter 9, Table 8
K = 12.9 ohms, copper
I = 86 ampere (74.8 amperes @115%), Table 430-150
D = 175 feet
VD 5% = 10.4 volts (208 volts x 5%)
CM = (1.732 x 12.9 ohms x 86 ampere x 175 feet)/10.4 volts
CM = 32,332, Chapter 9, Table 8 = No. 4
Caution: For voltage drop, the No. 4 wire is okay from the controller to the motor, but
Section 695-6(c)(2) requires the branch circuit conductors to be sized no less than No.
3.
I hope this short summary was helpfull. If you want to know more about this subject, please
attend our seminar or order our home study video program today.
Voltage Drop Homestudy Program (4 Hour CEU Credit)
Voltage drop calculations for branch circuits and feeders are explained in great detail.
Subjects covered include: wire sizing, maximum distance, voltage drop, and the effects
of, Harmonic currents, multi-wire branch circuits, copper versus aluminum, AC versus DC,
metallic versus nonmetallic raceways, skin effect and eddy currents. Includes Articles
210, 215, 230, 250 and 310. Textbook with 2-hour video - $79 [CLV3], Book only $25 [CLW3].
ORDERING INFORMATION
Mike Holt Enterprises, Inc.
7310 West McNab Road #201 Tamarac, Florida
E-Mail Sarina
Our office hours - 8:30 am (sometimes earlier) to 5:00 PM (sometimes later) Eastern standard
time.
- BY PHONE Toll Free, 1-888-NEC Code! When you call us, a real person will be there
to answer all of your questions courteously and promptly (no voice mail). If you call
before or after hours, simply place your order or leave a message on the answering
machine.
- PAYMENT, We accept VISA, Master Charge, American Express, Discover, personal and business
checks, money orders, and cash. Please make all checks and money orders payable to
Mike Holt Enterprises, Inc.
- SHIPMENT, Orders received by 1 PM, are shipped that day and orders received after
1 PM are shipped the next day (unless back-ordered). To receive your orders quickly
we must have your correct address, don't forget the Zip Code. We cannot ship to a
Post Office Box. Orders are shipped regular UPS, however Next Day, Second Day, Third
Day, and C.O.D. shipments are available.
- DON'T FORGET to include shipping and handling charges of $6 for orders less than $100
and 4% for orders over $100
|