Illustrated Changes to the NEC, 2005 Edition - Part 2

Article 406

Receptacles, Cord Connectors, and Attachment Plugs (Caps)

406.4 Receptacle Mounting

Text added to recognize the generally accepted practice, that receptacles mounted in boxes supported by a pendant flexible cord is permitted.

Receptacles must be installed in outlet boxes designed for the purpose, and the outlet box must be securely fastened in place, unless the outlet box for the receptacle is supported in accordance with 314.23.

Authorís Comment: 314.23(H) permits a pendant cord to support an outlet boxes [314.23(H)], but fittings on the outlet box must ensure that tension will not be transmitted to the conductor joints or terminals [400.10]. Figure 406-1