Battery Short Burns Up Wires (04-27-02)
 

Mike,

I am currently working on a project in Flagstaff, Arizona that involves the installation of a standby generator with a remote control panel. During the startup phase of the installation the manufacturer's representative disconnected the battery negative ground jumper. He said that since he would have to disconnect the batteries several times during the startup and tests that it would eliminate the possibility of a battery short. The batteries are two parallel sets of two batteries in series with a potential of over 13,000 amps at 24 volts. The first time he disconnected the batteries he pulled off one of the positive cables first, and dropped it behind the batteries. The cable met a conduit from the control panel, with the second cable still attached to the batteries. The fault current back fed the microprocessor through the ground and found a #14 control wire tied to the battery negative. The result was a fire in the control panel that burned a bundle of approximately ninety #14 wires. It took half of the day to replace the wires; fortunately, there was no damage to the microprocessor. The representative said that removing the negative ground jumper was standard procedure, and that he had never had a problem before. All I can say is that it does not seem like a very good practice. It would be better to follow the practice of removing the negative cables first, as you were taught in auto shop.

Michael White
Corbins Service Electric
Mwhite2690@aol.com

  Go to top of page

Newsletter Registration   |   Stay Connected:
 

888.NEC.CODE (632.2633) 3604 PARKWAY BLVD, STE 3, LEESBURG FL 34748  

Tell a Friend About This Site

  NEC® and National Electrical Code® are registered trade marks
of the National Fire Protection Association (NFPA).
  ©Copyright 2011 Mike Holt Enterprises, Inc.